Plan Review Notes
Plan Review Notes For Permit 22060690
Permit Number 22060690
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2022-08-22 11:15:53THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS AN INDICATION THAT THIS IS REVISION OF
 MASTER PERMIT # 21061851, WHICH DOESN'T SHOW
 CANOPY/AWNING WORK.
  
 PER NFPA 1
 1.14 PLAN REVIEW.
 1.14.5 WHEN REQUIRED BY THE AHJ, REVISED CONSTRUCTION
 DOCUMENTS OR SHOP DRAWINGS SHALL BE PREPARED AND
 SUBMITTED FOR REVIEW AND APPROVAL TO ILLUSTRATE
 CORRECTIONS OR MODIFICATIONS NECESSITATED BY FIELD
 CONDITIONS OR OTHER REVISIONS TO APPROVED PLANS.
  
 PLEASE SUBMIT PLANS THAT HAVE INDICATIONS WHERE THE
 REVISIONS OR MODIFICATIONS, FROM THE ORIGINAL PLANS,
 ARE LOCATED.
  
  
 1A) THERE IS NO SITE PLAN INDICATING THE LOCATIONS OF
 EACH PROPOSED CANOPY/AWNING.
  
 1.7.12 PLANS AND SPECIFICATIONS.
  
 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE
 PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH
 APPLICABLE CODES AND STANDARDS.
  
 1.7.12.2 PLANS SHALL BE SUBMITTED TO THE AHJ PRIOR TO
 CONSTRUCTION UNLESS OTHERWISE PERMITTED BY 1.7.11.4.
  
 PLEASE PROVIDE A DETAILED SITE PLAN.
  
  
 1B) THERE IS NO INDICATIONS OF THE DIMENSIONS OF EACH
 CANOPY.
  
 1.7.12 PLANS AND SPECIFICATIONS.
  
 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE
 PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH
 APPLICABLE CODES AND STANDARDS.
  
 1.7.12.2 PLANS SHALL BE SUBMITTED TO THE AHJ PRIOR TO
 CONSTRUCTION UNLESS OTHERWISE PERMITTED BY 1.7.11.4.
  
 1.7.12.6 PLANS SHALL BE SUBMITTED TO THE AHJ PRIOR TO
 THE ALTERATION OF THE MEANS OF EGRESS OR FIRE
 PROTECTION SYSTEMS OF ANY EXISTING BUILDING.
  
 PLEASE PROVIDE DETAILED DIMENSIONS OF EACH
 CANOPY/AWNING.
  
 1C) THERE IS NO INDICATION OF FLAME RETARDANT
 CERTIFICATION.
  
 PER NFPA 101
  
 11.9.1.6 FLAME PROPAGATION PERFORMANCE.
 11.9.1.6.1 ALL MEMBRANE STRUCTURE FABRIC SHALL MEET THE
 FLAME PROPAGA TION PERFORMANCE CRITERIA CONTAINED IN
 TEST METHOD 2 OF NFPA 701.
 11.9.1.6.2 ONE OF THE FOLLOWING SHALL SERVE AS EVIDENCE
 THAT THE FABRIC
 MATERIALS HAVE THE REQUIRED FLAME PROPAGATION
 PERFORMANCE:
 (1) THE AUTHORITY HAVING JURISDICTION SHALL REQUIRE A
 CERTIFICATE OR OTHER
 EVIDENCE OF ACCEPTANCE BY AN ORGANIZATION ACCEPTABLE TO
 THE AUTHOR ITY HAVING JURISDICTION.
 (2) THE AUTHORITY HAVING JURISDICTION SHALL REQUIRE A
 REPORT OF TESTS
 MADE BY OTHER INSPECTION AUTHORITIES OR ORGANIZATIONS
 ACCEPTABLE
 TO THE AUTHORITY HAVING JURISDICTION.
  
 PLEASE PROVIDE.
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  