2022-08-19 15:32:08PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT A SITE PLAN THAT SHOWS THE LOCATION OF THE
 PROPOSED AWNING. FBC AMENDMENTS 107.2.1
  
 2) SUBMIT AN ELEVATION OF THE BUILDING THAT SHOWS THE
 LOCATION OF THE AWNING ON THE BUILDING. SHOW THE HEIGHT
 OF THE AWNING ABOVE GRADE OR THE WALKWAY. FBC
 3105.3.1.1 FABRIC AWNINGS AND FABRIC-COVERED FRAMES
 LOCATED OVER PUBLIC PROPERTY OR IN AREAS ACCESSIBLE TO
 THE GENERAL PUBLIC SHALL BE CONSTRUCTED SO THAT NO
 RIGID PART OF SUCH FABRIC AWNINGS OR FABRIC-COVERED
 FRAMES SHALL BE LESS THAN 7 FEET 6 INCHES (2286 MM)
 FROM THE GRADE DIRECTLY BELOW, AND NO PART OF THE CLOTH
 DROP SHALL BE LESS THAN 7 FEET (2134 MM).
  
 3) PROVIDE ENGINEERED DETAILS OF THE AWNING FRAME
 CONSTRUCTION AND HOW IT WILL BE ATTACHED TO THE
 BUILDING. FBC 3105.4.2 DESIGN OF THE STRUCTURAL FRAMING
 MEMBERS SHALL BE BASED ON RATIONAL ANALYSIS, USING THE
 APPLICABLE WIND LOADS OF CHAPTER 16 AS SHOWN BELOW:
 3105.4.2.1 THE WIND DESIGN LOADS FOR ANY FABRIC OR
 MEMBRANE-COVERED STRUCTURE DESIGNED WITH A QUICK
 REMOVAL OR BREAKAWAY MEMBRANE OR FABRIC AT WIND
 VELOCITIES OF 75 MPH, SHALL BE BASED ON THE FOLLOWING
 CRITERIA:
 MINIMUM WIND SPEED 105 MPH
 EXPOSURE CATEGORY B, C OR D AS DEFINED IN CHAPTER 16.
  
 3105.4.2.2 THE WIND DESIGN LOADS FOR ANY FABRIC OR
 MEMBRANE COVERED STRUCTURE DESIGNED WITH A PERMANENT OR
 NONREMOVABLE FABRIC OR MEMBRANE, SHALL BE BASED ON THE
 FOLLOWING CRITERIA:
 MINIMUM WIND SPEED VELOCITY AS REQUIRED IN CHAPTER 16
 USING FIGURE 1609.3(4).
 EXPOSURE B, C OR D AS DEFINED IN CHAPTER 16.
  
 4) PROVIDE THE WIND DESIGN DATA FOR THE AWNING FRAME
 AND THE FABRIC MEMBRANE. FBC 3105.3 DESIGN AND
 CONSTRUCTION.AWNINGS AND CANOPIES SHALL BE DESIGNED AND
 CONSTRUCTED TO WITHSTAND WIND OR OTHER LATERAL LOADS
 AND LIVE LOADS AS REQUIRED BY CHAPTER 16 AND IN
 ACCORDANCE WITH SECTION 3105.4 OF THIS CODE WITH DUE
 ALLOWANCE FOR SHAPE, OPEN CONSTRUCTION AND SIMILAR
 FEATURES THAT RELIEVE THE PRESSURES OR LOADS.
 STRUCTURAL MEMBERS SHALL BE PROTECTED TO PREVENT
 DETERIORATION. AWNINGS SHALL HAVE FRAMES OF
 NONCOMBUSTIBLE MATERIAL, FIRE-RETARDANT-TREATED WOOD,
 HEAVY TIMBER COMPLYING WITH SECTION 2304.11, OR 1-HOUR
 CONSTRUCTION WITH COMBUSTIBLE OR NONCOMBUSTIBLE COVERS
 AND SHALL BE EITHER FIXED, RETRACTABLE, FOLDING OR
 COLLAPSIBLE.
  
 5) PROVIDE THE FIRE TEST REPORTS FOR THE FABRIC AWNING.
 FBC 3105.3.4.1 FABRIC USED FOR AWNINGS OR
 FABRIC-COVERED FRAMES SHALL MEET THE FLAME PROPAGATION
 PERFORMANCE CRITERIA OF NFPA 701 OR HAVE A FLAME SPREAD
 INDEX NOT GREATER THAN 25 WHEN TESTED IN ACCORDANCE
 WITH ASTM E84 OR UL 723.
  
 6) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH
 OF THE REVIEW COMMENTS HAS BEEN ADDRESSED.