Plan Review Notes
Plan Review Notes For Permit 22060686
Permit Number 22060686
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2022-06-22 14:35:45FIRE REVIEW COMMENTS:
  
 1.) A PROJECT OF THIS SIZE IS RECOMMENDED TO HAVE TWO
 FIRE DEPARTMENT CONNECTIONS AND TWO FIRE HYDRANTS FOR
 FIRE GROUND OPERATIONAL TACTICS AND STRATEGIES.
  
 2.) ALL UNDERGROUND FIRE LINE WORK SHALL BE INSTALLED
 UNDER SEPARATE PERMITS AND SHOP DRAWINGS, INCLUDING
 MANUFACTURES SPECIFICATION SHEETS. PLEASE PROVIDE AN
 APPLICABLE NOTE OF ACKNOWLEDGEMENT.
  
 3.) NFPA 241
 8.7.4.2 STANDPIPE INSTALLATIONS IN BUILDINGS UNDER
 CONSTRUCTION.
 WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION, IN
 BUILDINGS UNDER CONSTRUCTION, A STANDPIPE SYSTEM,
 EITHER TEMPORARY OR PERMANENT IN NATURE, SHALL BE
 INSTALLED IN ACCORDANCE WITH 8.7.4.2.1 THROUGH
 8.7.4.2.10.
 STANDPIPE CONNECTIONS, AT LEAST ONE FOR THE APARTMENT
 BUILDING AND ONE FOR THE PARKING GARAGE, WITH FDC?S,
 SHALL BE INSTALLED BEGINNING WITH THE 4TH FLOOR. PLEASE
 PROVIDE AN APPLICABLE NOTE OF ACKNOWLEDGEMENT.
  
 4.) NFPA 14
 4.7.2 HOSE CONNECTIONS SHALL HAVE EXTERNAL NATIONAL
 HOSE STANDARD (NHS) THREADS, FOR THE VALVE SIZE
 SPECIFIED, IN ACCORDANCE WITH NFPA 1963, STANDARD FOR
 FIRE HOSE CONNECTIONS, THE PLAN INDICATES MIAMI
 THREADS.
  
 5.) 6.4.5.1 FIRE DEPARTMENT CONNECTIONS SHALL BE
 VISIBLE AND RECOGNIZABLE FROM THE STREET OR NEAREST
 POINT OF FIRE DEPARTMENT APPARATUS ACCESSIBILITY OR ON
 THE STREET SIDE OF BUILDINGS.
  
 6.) 6.4.5.4* FIRE DEPARTMENT CONNECTIONS SHALL BE
 LOCATED NOT MORE THAN 100 FT (30.5 M) FROM THE NEAREST
 FIRE HYDRANT CONNECTED TO AN APPROVED WATER SUPPLY.
 PROVIDE THE DISTANCE FROM THE EXISTING FIRE HYDRANT TO
 THE FDC.
  
 7.) 7.3.2.2* WHERE THE MOST REMOTE PORTION OF A
 NON-SPRINKLERED FLOOR OR STORY IS LOCATED IN EXCESS OF
 150 FT (45.7 M) OF TRAVEL DISTANCE FROM A HOSE
 CONNECTION IN OR ADJACENT TO A REQUIRED EXIT OR THE
 MOST REMOTE PORTION OF A SPRINKLERED FLOOR OR STORY IS
 LOCATED IN EXCESS OF 200 FT (61 M) OF TRAVEL DISTANCE
 FROM A HOSE CONNECTION IN OR ADJACENT TO A REQUIRED
 EXIT, ADDITIONAL HOSE CONNECTIONS SHALL BE PROVIDED, IN
 APPROVED LOCATIONS, WHERE REQUIRED BY THE LOCAL FIRE
 DEPARTMENT OR THE AHJ.
 THE MEASUREMENT NEEDS TO BE FROM THE HOSE CONNECTION TO
 THE MOST REMOTE PORTION WITHIN A LIVING UNIT OR OTHER
 APPLICABLE REMOTE AREA. PLEASE REVIEW AND PROVIDE
 GREATER DETAILED MEASUREMENTS AND CORRECT AS
 APPLICABLE.
  
 8.) THERE ARE NO INDICATIONS OF TWO-WAY EMERGENCY RADIO
 COMMUNICATIONS.
 NFPA 1
 11.10* TWO-WAY RADIO COMMUNICATION ENHANCEMENT
 SYSTEMS.
 11.10.1 IN ALL NEW AND EXISTING BUILDINGS, MINIMUM
 RADIO SIGNAL STRENGTH FOR FIRE DEPARTMENT
 COMMUNICATIONS SHALL BE MAINTAINED AT A LEVEL
 DETERMINED BY THE AHJ.
 11.10.2 WHERE REQUIRED BY THE AHJ, TWO-WAY RADIO
 COMMUNICATION
 ENHANCEMENT SYSTEMS SHALL COMPLY WITH NFPA 72.
 11.10.3 WHERE A TWO-WAY RADIO COMMUNICATION ENHANCEMENT
 SYSTEM IS REQUIRED AND SUCH SYSTEM, COMPONENTS, OR
 EQUIPMENT HAS A NEGATIVE IMPACT ON THE NORMAL
 OPERATIONS OF THE FACILITY AT WHICH IT IS INSTALLED,
 THE AHJ SHALL HAVE THE AUTHORITY TO ACCEPT AN
 AUTOMATICALLY ACTIVATED RESPONDER SYSTEM.
 ALL BDA WORK SHALL BE INSTALLED UNDER SEPARATE PERMIT
 AND SHOP DRAWINGS. PLEASE PROVIDE AN APPLICABLE NOTE OF
 ACKNOWLEDGEMENT.
  
 9.) ALL FIRE ALARM WORK SHALL BE UNDER SEPARATE PERMIT
 AND SHOP DRAWINGS. PLEASE PROVIDE AN APPLICABLE NOTE OF
 ACKNOWLEDGEMENT.
  
 10.) ALL FIRE SPRINKLER WORK SHALL BE UNDER SEPARATE
 PERMIT AND SHOP DRAWINGS. PLEASE PROVIDE AN APPLICABLE
 NOTE OF ACKNOWLEDGEMENT.
  
 11.) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 LISTED ITEMS.
  
 12.) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RESUBMITTAL OF THE ABOVE.
  
 FIRE REVIEW BY:
  
 C. WALKER
  
 (561) 804-4762
  
 [email protected]
  
  
  