Plan Review Notes
Plan Review Notes For Permit 22060671
Permit Number 22060671
Review Stop P
Sequence Number 1
Notes
Date Text
2022-07-05 12:33:381ST PLUMBING REVIEW
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2020 FPC 1003.3.1 - ONLY DEVICES DESIGNED TO RECEIVE
 FATS, OILS AND GREASE SHALL BE DIRECTED TO THE GREASE
 WASTE. PLEASE SHOW THAT THE ICE BIN, HAND SINK,
 DRINKING FOUNTAIN/ICE BIN COMBOS, AND OTHER DEVICES
 THAT ARE NOT DESIGNED TO RECEIVE F.O.G DISCHARGES ARE
 GOING TO THE SANITARY AND NOT TO THE GREASE WASTE.
 PLEASE CLARIFY YOUR DRAWING TO SHOW THE SEPARATION OF
 GREASE WASTE AND SANITARY WASTE.
  
 2. 2020 FPC - 607.1.1 - PLEASE INDICATE THAT THE HOT
 WATER IS IN COMPLIANCE WITH 607.1.1. A THERMOSTATIC
 MIXING DEVICE SHALL BE INSTALLED ON THE HOT WATER
 DELIVERY SYSTEM. IF THERE IS NOT ONE, IT SHALL BE
 ADDED. THIS REQUIREMENT FOR HOT WATER DELIVERY
 PROTECTION IS IN ADDITION TO THE REQUIREMENTS FOR
 TEMPERED WATER DELIVERY REQUIRED BY 607.1.2.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR