Plan Review Notes For Permit 22060621 |
Permit Number |
22060621 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2022-06-17 12:12:10 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) THERE ARE INDICATIONS OF PROPOSED BOOTH SEATING | | EXTENSION AND PIZZA AREA COUNTERTOPS BY THE EXISTING | | EXIT DOOR. | | | | | | THERE IS NO DIMENSION SHOWING THE DISTANCE BETWEEN THE | | CHAIRS AND THE COUNTERTOP AT THE ROUND TABLE AND THE | | DIAGONAL AREA AT THE CORNER CHAIR AND CORNER OF THE | | COUNTERTOP(BOTH SIDES) THAT MEETS THE MINIMUM EXIT | | WIDTH REQUIRMENTS PER NFPA 101. | | | | CH 12 NEW ASSEMBLY OCCUPANCIES | | | | 12.2.5.4.2* ACCESS AND EGRESS ROUTES SHALL BE | | MAINTAINED SO THAT ANY | | INDIVIDUAL IS ABLE TO MOVE WITHOUT UNDUE HINDRANCE, ON | | PERSONAL INITIA TIVE AND AT ANY TIME, FROM AN OCCUPIED | | POSITION TO THE EXIT | | | | 12.2.5.6.3* MINIMUM AISLE WIDTH. THE MINIMUM CLEAR | | WIDTH OF | | AISLES SHALL BE SUFFICIENT TO PROVIDE EGRESS CAPACITY | | IN ACCORDANCE WITH | | 12.2.3.1 BUT SHALL BE NOT LESS THAN THE FOLLOWING: | | | | (5) 36 IN. (915 MM) FOR LEVEL OR RAMPED AISLES HAVING | | SEATING ON ONLY | | ONE SIDE | | | | PLEASE REVIEW AND PROVIDE THE ACTUAL DIMENSIONS THAT | | INDICATE THE MINIMUM REQUIREMENT. | | | | | | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | ABOVE. | | | | | | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | RE-SUBMITTAL OF THE ABOVE. | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | | | | | |
|