Plan Review Notes
Plan Review Notes For Permit 22060621
Permit Number 22060621
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2022-06-17 12:12:10THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE ARE INDICATIONS OF PROPOSED BOOTH SEATING
 EXTENSION AND PIZZA AREA COUNTERTOPS BY THE EXISTING
 EXIT DOOR.
  
  
 THERE IS NO DIMENSION SHOWING THE DISTANCE BETWEEN THE
 CHAIRS AND THE COUNTERTOP AT THE ROUND TABLE AND THE
 DIAGONAL AREA AT THE CORNER CHAIR AND CORNER OF THE
 COUNTERTOP(BOTH SIDES) THAT MEETS THE MINIMUM EXIT
 WIDTH REQUIRMENTS PER NFPA 101.
  
 CH 12 NEW ASSEMBLY OCCUPANCIES
  
 12.2.5.4.2* ACCESS AND EGRESS ROUTES SHALL BE
 MAINTAINED SO THAT ANY
 INDIVIDUAL IS ABLE TO MOVE WITHOUT UNDUE HINDRANCE, ON
 PERSONAL INITIA TIVE AND AT ANY TIME, FROM AN OCCUPIED
 POSITION TO THE EXIT
  
 12.2.5.6.3* MINIMUM AISLE WIDTH. THE MINIMUM CLEAR
 WIDTH OF
 AISLES SHALL BE SUFFICIENT TO PROVIDE EGRESS CAPACITY
 IN ACCORDANCE WITH
 12.2.3.1 BUT SHALL BE NOT LESS THAN THE FOLLOWING:
  
 (5) 36 IN. (915 MM) FOR LEVEL OR RAMPED AISLES HAVING
 SEATING ON ONLY
 ONE SIDE
  
 PLEASE REVIEW AND PROVIDE THE ACTUAL DIMENSIONS THAT
 INDICATE THE MINIMUM REQUIREMENT.
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  