2022-07-01 12:20:08 | 1ST REVIEW FMC | | PERMIT: 22060616 | | | | CODES IN EFFECT: 2020 | | | | FBC- FLORIDA BUILDING CODE | | FMC- FLORIDA MECHANICAL CODE | | FEC- FLORIDA ENERGY CONSERVATION | | FGC- FLORIDA FUEL GAS | | FEX- FLORIDA EXISTING BUILDING CODE | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | F.S.- FLORIDA STATUTES | | FAC- FLORIDA ACCESSIBILITY CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) SHEET 1 OF 13 OF THE ENERGY CALCULATIONS INDICATES 1 | | STRUCTURE WITH 2482 SQ FT. THE DRAWINGS SUBMITTED | | INDICATE A MAIN HOUSE AND A 2 STORY GARAGE WITH | | STORAGE. THE GARAGE WITH STORAGE IS BEING CONVERTED SO | | A SEPARATE PERMIT WILL BE REQUIRED FOR THIS CHANGE OF | | USE. THE ENERGY CODE MUST REFLECT THE 2 SEPARATE | | STRUCTURES. PROVIDE AN ENERGY CALCULATION FOR THE MAIN | | HOUSE AND ONE FOR THE GUEST HOUSE SEPARATELY. FBC | | 107.2.1 | | | | 2) THE MECHANICAL EQUIPMENT SIZING CALCULATIONS SHOULD | | CLEARLY DISTINGUISH THE MAIN HOUSE FROM THE GUEST | | HOUSE. SUBMIT A MECHANICAL CALCULATION FOR EACH. FBC | | 107.2.1 | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM. | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | |
|