Plan Review Notes
Plan Review Notes For Permit 22060616
Permit Number 22060616
Review Stop G
Sequence Number 1
Notes
Date Text
2022-07-01 09:18:581ST REVIEW FBC-2020 RES. GAS
 PERMIT- 22060616
 7/1/22
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. PLEASE NOTE THAT SEPARATE
 PERMITS ARE REQUIRED FOR THE MAIN HOUSE AND GUEST
 HOUSE. THE FOLLOWING REVIEW APPLIES TO BOTH
 OCCUPANCIES.
  
 1) SHEETS P-1 & P-3: PROVIDE EQUIPMENT SCHEDULES FOR
 THE TANKLESS WATER HEATERS AND SUBMIT MANUFACTURER'S
 SPECIFICATIONS AND INSTALLATION MANUALS- SEC.G2448.1
 FBC RES.
  
 2) P-1 & P-3: PROVIDE AN EQUIPMENT SCHEDULE FOR THE NEW
 RANGE AND SUBMIT MANUFACTURER'S SPECIFICATIONS- SECTION
 G2447.1 FBC RES. A) PROVIDE COMBUSTION AIR CALCULATIONS
 AND INDICATE HOW THE AIR WILL BE PROVIDED- SECTION
 G2407.1 FBC RES.
  
 3) P-1 & P-3: PROVIDE AN EQUIPMENT SCHEDULE FOR THE NEW
 DRYER AND SUBMIT MANUFACTURER'S SPECIFICATIONS- SECTION
 G2447.1 FBC RES. A) INDICATE HOW MAKEUP AIR WILL BE
 PROVIDED IN ACCORDANCE WITH G2407.1 & G2439.5 FBC RES.
  
 4) P-1 & P-3: THE PLANS SHOW AN EXISTING FIREPLACE.
 VERIFY IT IS NOT A GAS FIREPLACE, OR SHOW THE GAS
 PIPING ON THE RISER DRAWING- SEC. 107.2.1 WPB.
  
 5) P-3: SHOW THE CUT PIPING LENGTHS AND TOTAL PIPING
 RUN LENGTHS FROM THE LOW-PRESSURE REGULATORS TO THE
 RANGE AND THE DRYER- SEC. G2413.4.1 FBC RES.
  
 6) P3: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 REGULATORS MARKED UP TO SHOW THE SELECTED MODELS, AND
 INPUT AND OUT PIPE SIZES AND PRESSURES- SECTION G2421.2
 FBC RES.
  
 7) P-1 & P-3: PROVIDE CONDENSATE DISPOSAL PIPING
 DETAILS FOR THE WATER HEATERS- SEC. 307.2 FBC FG.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  