2022-06-15 10:43:28 | 1ST REVIEW FBC-2020 RES. GAS |
| PERMIT- 22060733 |
| 6/15/2022 |
| |
| CODES IN EFFECT: |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| 2020 |
| FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) I WAS UNABLE TO LOCATE ANY PREVIOUS GAS PIPING |
| PERMIT RECORDS FOR 731 HIGH ST., AND UNABLE TO VERIFY |
| THE EXISTING 1-1/4 GALVANIZED UNDERGROUND GAS PIPING |
| WAS LEGALLY PERMITTED AND INSPECTED- SECS. 105.1 & |
| 107.2.1 WPB. IT APPEARS THAT THE GAS PIPING TO THE POOL |
| HEATER AND ANY OTHER "EXISTING" GAS PIPING AT THE |
| RESIDENCE MUST BE REVIEWED AND APPROVED AS NEW |
| INSTALLATIONS. PLEASE PROVIDE A COMPLETE GAS RISER |
| DRAWING THAT INCLUDES ALL NEW AND EXISTING GAS PIPING |
| AND APPLIANCES AT THE RESIDENCE- SECTION G2412.3 & |
| G2412.4 FBC RES. REFER TO FBC RES. CHAPTER 24 FUEL GAS- |
| THE RISER SHALL INDICATE: |
| A) TYPE OF GAS- NATURAL OR LP. |
| B) DELIVERY PRESSURE AT THE METER. |
| C) TOTAL BTU LOAD AND INDIVIDUAL APPLIANCE BTU LOADS. |
| D) TYPES AND SIZES OF PIPING. |
| E) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER |
| TO THE MOST REMOTE APPLIANCE OUTLET. |
| F) BRANCH AND CUT PIPE LENGTH MEASUREMENTS. |
| G) LOCATIONS OF REGULATORS, SHUTOFF VALVES, AND PIPE |
| UNIONS. |
| H) OUTLET PRESSURES AT REGULATORS. |
| I) LOCATIONS AND TYPES OF PIPE SLEEVES. |
| K) PIPE SIZING TABLES. |
| |
| 2) PROVIDE A BASIC SITE PLAN THAT SHOWS THE LOCATION OF |
| THE POOL HEATER WITH CLEARANCE DISTANCE MEASUREMENTS TO |
| THE BUILDING, WINDOW AND DOOR OPENINGS, AND OTHER AIR |
| INTAKES INTO THE BUILDING- SECS. G2427.8, AND G2441.1 |
| FBC RES. |
| |
| 3) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE POOL |
| HEATER- SEC. G2441.1 FBC RES. |
| |
| 4) PLEASE NOTE THE RESUBMITTED RISER SHALL INCLUDE THE |
| ADDRESS OF THE PROPERTY, AND THE PRINTED NAME AND |
| SIGNATURE OF THE CONTRACTOR OR QUALIFIER WHO PREPARED |
| THE DRAWING- SEC. 107.2.1 WPB. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |