Plan Review Notes
Plan Review Notes For Permit 22060459
Permit Number 22060459
Review Stop E
Sequence Number 3
Notes
Date Text
2022-12-22 11:46:36ELECTRIC REVIEW FAILED
 1) PREVIOUS COMMENTS ADDRESSED INCORRECTLY. PLEASE
 PROVIDE A CORRECT RISER DIAGRAM. NEC 215.5
 2) IT APPEARS THE ELECTRIC PANEL IN THE KITCHEN DOES
 NOT COMPLY WITH NEC 110.26 FOR WORKING CLEARANCES.
 PLEASE CORRECT AS APPLICABLE.
  
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  