Date |
Text |
2022-08-24 16:18:54 | BUILDING REVIEW COMMENTS: |
| |
| W.P.B. PERMIT: 22060459 |
| REVIEWED: AUGUST 24, 2022 |
| |
| DYLAN BATTLES |
| BUILDING PLANS EXAMINER PX4191 |
| [email protected] |
| 561-805-6718 |
| |
| FLORIDA BUILDING CODE,7TH EDITION (2020) |
| FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK |
| BELOW) |
| HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/ |
| BUILDING-PERMIT-FORMS |
| FBC[EXISTING] = FBC EXISTING BUILDING |
| FBC[E] = FBC ENERGY CONSERVATION |
| FBC[R] = FBC RESIDENTIAL |
| |
| 1. 311.3 FBC[R] FLOORS AND LANDINGS AT EXTERIOR DOORS. |
| THERE SHALL BE A LANDING OR FLOOR ON EACH SIDE OF EACH |
| EXTERIOR DOOR. THE WIDTH OF EACH LANDING SHALL BE NOT |
| LESS THAN THE DOOR SERVED. EVERY LANDING SHALL HAVE A |
| DIMENSION OF NOT LESS THAN 36 INCHES (914 MM) MEASURED |
| IN THE DIRECTION OF TRAVEL. THE SLOPE AT EXTERIOR |
| LANDINGS SHALL NOT EXCEED 1/4 UNIT VERTICAL IN 12 UNITS |
| HORIZONTAL (2 PERCENT). |
| - PROVIDE LANDING AT EXTERIOR SIDE OF DOORS IF GREATER |
| THAN 2 RISERS PROVIDED. |
| |
| 2. 408.1 FBC[R] VENTILATION. THE UNDER-FLOOR SPACE |
| BETWEEN THE BOTTOM OF THE FLOOR JOISTS AND THE EARTH |
| UNDER ANY BUILDING (EXCEPT SPACE OCCUPIED BY A |
| BASEMENT) SHALL HAVE VENTILATION OPENINGS THROUGH |
| FOUNDATION WALLS OR EXTERIOR WALLS. |
| - PLEASE PROVIDE THE AMOUNT OF EXISTING UNDER FLOOR |
| VENTILATION AND SHOW WHERE ACCESS PANEL IS LOCATED. IT |
| APPEARS THAT THE ADDITION MAY BLOCK SOME OF THE OLD |
| VENTS SO A NEW CALCULATION SHOULD BE DONE FOR THE |
| EXISTING AND IF ANY NEW CRAWL SPACE IS BEING DONE. |
| |
| PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F |
| 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME |
| [email protected] |
| |
| |
| |