Plan Review Notes
Plan Review Notes For Permit 22060412
Permit Number 22060412
Review Stop B
Sequence Number 1
Notes
Date Text
2022-06-08 08:47:52JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR EMAIL [email protected].
  
 1. FBC B 107.2.1. SUBMITTED FLORIDA DBPR PRODUCT
 APPROVAL FL16709-R9 HAS BEEN REVISED TO FL16709-R10.
 PLEASE PROVIDE THE FOLLOWING: INCLUDE COVER PAGE,
 EVALUATION REPORT PAGES 1-4 AND INSTALLATION
 INSTRUCTIONS FOR SYSTEM USED. ALL APPLICABLE DETAILS
 AND ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON THE
 PRODUCT APPROVAL DRAWINGS.
 2. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT
 APPROVAL FL16709-R9 SELECTED OPTION FOR SYSTEM NO W-4;
 EXPOSURE (C); ENCLOSURE (ENCLOSED); ROOF HEIGHT (H<15);
 ULTIMATE WIND SPEED (170) IS NOT CORRECT. THE CORRECT
 EXPOSURE FOR THE LISTED ADDRESS IS EXPOSURE D. PRODUCT
 APPROVAL FL16709-R9 WILL NOT SATISFY EXPOSURE CATEGORY
 D ENCLOSED AREAS WITHOUT USING INSULATION OR PROVIDING
 ENGINEERED ENHANCED NAILING.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMEMTS.
  