2022-06-08 08:47:52 | JONATHAN BROOKS JR. |
| BUILDING PLANS EXAMINER |
| WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM |
| PHONE (561) 805-6656 |
| EMAIL: [email protected] |
| |
| 1ST REVIEW: FBC 2020 7TH EDITION |
| FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| FBC B = FBC BUILDING |
| FBC R = FBC RESIDENTIAL |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| CITY HALL, OR EMAIL [email protected]. |
| |
| 1. FBC B 107.2.1. SUBMITTED FLORIDA DBPR PRODUCT |
| APPROVAL FL16709-R9 HAS BEEN REVISED TO FL16709-R10. |
| PLEASE PROVIDE THE FOLLOWING: INCLUDE COVER PAGE, |
| EVALUATION REPORT PAGES 1-4 AND INSTALLATION |
| INSTRUCTIONS FOR SYSTEM USED. ALL APPLICABLE DETAILS |
| AND ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON THE |
| PRODUCT APPROVAL DRAWINGS. |
| 2. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT |
| APPROVAL FL16709-R9 SELECTED OPTION FOR SYSTEM NO W-4; |
| EXPOSURE (C); ENCLOSURE (ENCLOSED); ROOF HEIGHT (H<15); |
| ULTIMATE WIND SPEED (170) IS NOT CORRECT. THE CORRECT |
| EXPOSURE FOR THE LISTED ADDRESS IS EXPOSURE D. PRODUCT |
| APPROVAL FL16709-R9 WILL NOT SATISFY EXPOSURE CATEGORY |
| D ENCLOSED AREAS WITHOUT USING INSULATION OR PROVIDING |
| ENGINEERED ENHANCED NAILING. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMEMTS. |
| |