Plan Review Notes
Plan Review Notes For Permit 22060411
Permit Number 22060411
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2022-06-09 14:56:10THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE IS AN INDICATION OF AN INFILL OF AN EXTERIOR
 DOOR; HOWEVER, THERE IS NO INDICATION OF THE
 CONSTRUCTION FEATURES OF THE NEW WALL OR/AND IF THE
 EXISTING DOOR IS TO REMAIN ON THE EXTERIOR.
  
 PER NFPA
  
 1.7.12 PLANS AND SPECIFICATIONS.
  
 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE
 PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH
 APPLICABLE CODES AND STANDARDS
  
 PLEASE PROVIDE DETAILS OF THE INTERIOR WALL.
  
 SHOULD THE EXTERIOR DOOR REMAIN, A SIGN IS REQUIRED TO
 BE POSTED ON THE DOOR "NO ENTRY THIS DOOR" OR EQUAL, SO
 THAT FF'S KNOW THEY CAN NOT ENTER THAT DOOR IN AN
 EMERGENCY.
  
 PLEASE REVIEW AND PROVIDE THE REQUIRED NOTE ON THE NEW
 PLAN SHEET.
  
  
  
  
 2) THERE IS AN INDICATION OF RECONFIGURATION OF THE
 KITCHEN AREA; HOWEVER, THE SCOPE OF WORK SHEET DOES NOT
 INDICATE FLOORING.
  
 PER NFPA
  
 1.7.12 PLANS AND SPECIFICATIONS.
  
 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE
 PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH
 APPLICABLE CODES AND STANDARDS
  
 PLEASE PROVIDE FLOORING DETAILS.
  
  
  
 2A) SHOULD THERE BE PROPOSED NEW FLOORING A FLOOR
 UNDERLAYMENT AND FLOOR MATERIAL/FINISH/TYPE SHOULD BE
 SUBMITTED WITH SPECIFICATIONS SHEETS THAT INDICATE
 MEETING THE REQUIREMENTS PER NFPA'
  
 PER NFPA 101, CH 30
  
 30.3.3.3 INTERIOR FLOOR FINISH.
 30.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN
 ACCORDANCE WITH
 SECTION 10.2.
  
 10.2.7* INTERIOR FLOOR FINISH TESTING AND
 CLASSIFICATION.
 10.2.7.1* CARPET AND CARPET LIKE INTERIOR FLOOR
 FINISHES SHALL
 COMPLY WITH ASTM D 2859, STANDARD TEST METHOD FOR
 IGNITION
 CHARACTERISTICS OF FINISHED TEXTILE FLOOR COVERING
 MATERIALS.
 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH
 10.2.2.2
 ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL
 HAVE A
 MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2.
  
 10.2.7.4 INTERIOR FLOOR FINISHES SHALL BE GROUPED IN
 THE CLASSES SPECIFIED
 IN 10.2.7.4.1 AND 10.2.7.4.2 IN ACCORDANCE WITH THE
 CRITICAL RADIANT FLUX
 REQUIREMENTS.
 10.2.7.4.1 CLASS I INTERIOR FLOOR FINISH. CLASS I
 INTERIOR FLOOR FINISH
 SHALL HAVE A CRITICAL RADIANT FLUX OF NOT LESS THAN
 0.45 W/CM2, AS DETERMINED
 BY THE TEST DESCRIBED IN 10.2.7.3.
 10.2.7.4.2 CLASS II INTERIOR FLOOR FINISH. CLASS II
 INTERIOR FLOOR FINISH
 SHALL HAVE A CRITICAL RADIANT FLUX OF NOT LESS THAN
 0.22 W/CM2, BUT LESS
 THAN 0.45 W/CM2, AS DETERMINED BY THE TEST DESCRIBED IN
 10.2.7.3.
  
  
 IF THE PROPOSED IS PORCELAIN OR CERAMIC TILE, NATURAL
 STONE TILE, CONCRETE TILES, SPEC SHEETS FOR THE FLOOR
 FINISH WOULD NOT BE REQUIRED.
  
 PLEASE REVIEW AND PROVIDE SPEC SHEETS.
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  