2022-08-15 14:34:402ND REVIEW FBC-2020 RES. GAS
 PERMIT- 22060317
 8/15/22
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) P-4: THE PLAN AND RISER SHOW PE PIPE RUN UNDER THE
 MAIN BUILDING TO THE RANGE, AND UNDER THE POOL CABANA
 BUILDING TO THE BBQ GRILL WHICH IS NOT PERMITTED- SEC.
 G2415.17.1 (404.17.1) FBC RES. THE ENGINEER MUST
 PROVIDE AN ALTERNATIVE SUCH AS CSST PIPING. IT APPEARS
 PE IS ALSO RUNNING UNDER THE LOGGIA SLAB TO THE
 FIREPLACE WHICH IS PERMITTED, HOWEVER PLEASE INDICATE
 THE BURIAL DEPTH OF THE PIPE TO SHOW COMPLIANCE WITH
 SECS. G2415.17.1 & G2415.12.1 FBC RES.
  
 2) P-4: PLEASE SUBMIT MANUFACTURER'S SPECS FOR THE BBQ
 GRILL- SEC. THE GRILL SHALL BE INSTALLED IN ACCORDANCE
 WITH THE MANUFACTURER'S GUIDELINES WHICH MAY REQUIRE A
 HOOD EXHAUST SYSTEM- G2447.1 FBC RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  