Plan Review Notes For Permit 22060317 |
Permit Number |
22060317 |
|
Review Stop |
G |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2022-08-15 14:34:40 | 2ND REVIEW FBC-2020 RES. GAS | | PERMIT- 22060317 | | 8/15/22 | | | | CODES IN EFFECT: | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | 2020 | | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 | | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION | | 2020 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) P-4: THE PLAN AND RISER SHOW PE PIPE RUN UNDER THE | | MAIN BUILDING TO THE RANGE, AND UNDER THE POOL CABANA | | BUILDING TO THE BBQ GRILL WHICH IS NOT PERMITTED- SEC. | | G2415.17.1 (404.17.1) FBC RES. THE ENGINEER MUST | | PROVIDE AN ALTERNATIVE SUCH AS CSST PIPING. IT APPEARS | | PE IS ALSO RUNNING UNDER THE LOGGIA SLAB TO THE | | FIREPLACE WHICH IS PERMITTED, HOWEVER PLEASE INDICATE | | THE BURIAL DEPTH OF THE PIPE TO SHOW COMPLIANCE WITH | | SECS. G2415.17.1 & G2415.12.1 FBC RES. | | | | 2) P-4: PLEASE SUBMIT MANUFACTURER'S SPECS FOR THE BBQ | | GRILL- SEC. THE GRILL SHALL BE INSTALLED IN ACCORDANCE | | WITH THE MANUFACTURER'S GUIDELINES WHICH MAY REQUIRE A | | HOOD EXHAUST SYSTEM- G2447.1 FBC RES. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. | | | | CHRISTOPHER L. COLE | | MECHANICAL/PLUMBING PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | | | |
|