2022-07-26 08:11:331ST REVIEW FBC-2020 RES. GAS
 PERMIT- 22060317
 7/26/22
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P-4: THE 3/4-INCH SCHEDULE 40 METALLIC SUPPLY
 PIPE FROM THE METER AND THE 3/4-INCH PE MAIN
 UNDERGROUND PIPE ARE UNDERSIZED BASED ON THE TABLES
 SHOWN ON THE PLAN- TABLES 402.4(5) & 402.4(22), AND
 SEC. G2413.4.1 (402.4.1) FBC RES. THE 3/4-INCH METALLIC
 IS LIMITED TO A TOTAL CAPACITY OF 695 CFH (695,000 BTU)
 AT 175 FT. TOTAL DEVELOPED LENGTH. THE 3/4-INCH PE IS
 LIMITED TO A TOTAL CAPACITY OF 791 CFH (791,000 BTU) AT
 TOTAL DEVELOPED LENGTH OF 175 FT. THE CALCULATIONS ON
 THE PLAN INDICATE THE TOTAL LOAD OF THE SYSTEM IS
 1,194,000 BTU AT A TOTAL DEVELOPED LENGTH OF 176'-8".
 CORRECT THE RISER AND THE PLAN:
 A) INCREASE THE DIAMETER OF THE SCHED. 40 PIPE TO
 MINIMUM 1-INCH.
 B) INCREASE THE DIAMETER OF THE PE PIPE TO MINIMUM
 1-INCH FOR THE PIPE RUN FROM THE SCHED. 40 TO A POINT
 BEYOND THE BRANCH CONNECTIONS TO THE WATER HEATERS.
 C) PIPE SIZES ARE BASED ON REDUCING THE TDL TO 175 FT.
 OTHERWISE THE SCHED. 40 PIPE SHALL BE INCREASED TO
 1-1/4-INCH.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  