Plan Review Notes
Plan Review Notes For Permit 22060301
Permit Number 22060301
Review Stop M
Sequence Number 3
Notes
Date Text
2022-12-13 08:55:331) SHEET M.0: THE OUTDOOR AIR SUMMARY TABLE SPECIFIES
 1160 CFMS OF OUTDOOR AIR IS REQUIRED. THE EXISTING
 ROOFTOP SCHEDULE SPECIFIES THAT EACH OF THE 3 RTUS WILL
 SUPPLY 290 CFMS, WHICH IS ONLY 870 CFMS. PROVIDE THE
 REQUIRED OUTDOOR AIR FOR THE SPACE. FMC TABLE 403.3.1.1
  
 2) I DO NOT SEE THE SPECIFICATIONS ASKED FOR IN COMMENT
 3 OF 2ND REVIEW CYCLE. PROVIDE DOCUMENTATION THAT SHOWS
 THE FABRIC DUCT IS LISTED AND LABELED IN COMPLIANCE
 WITH UL 2518. FMC 603.17
  