2022-09-30 06:28:451ST REVIEW FMC
 PERMIT: 22060301
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) 2ND ATTEMPT: PLEASE PROVIDE THE OUTDOOR AIR
 CALCULATIONS FOR THE OCCUPANCY FOR THESE 2 NEW RTU???S.
 FMC 403.3.1.1 AND TABLE 403.3.1.1
  
 2) SHEET M-1 SHOWS THE DUCT SMOKE DETECTOR LOCATION AS
 BEING IN THE RETURN DUCT. PLEASE SHOW THE DUCT SMOKE
 DETECTORS AS BEING LOCATED IN THE SUPPLY DUCT. FMC
 606.2.1
  
 606.2.1 TO PREVENT THE RECIRCULATION OF DANGEROUS
 QUANTITIES OF SMOKE, A DETECTOR APPROVED FOR AIR DUCT
 USE SHALL BE INSTALLED ON THE SUPPLY SIDE OF
 AIR-HANDLING SYSTEMS AS REQUIRED BY NFPA 90A, STANDARD
 FOR THE INSTALLATION OF AIR CONDITIONING AND
 VENTILATING SYSTEMS. SMOKE DETECTORS LISTED FOR USE IN
 AIR DISTRIBUTION SYSTEMS SHALL BE
 LOCATED DOWNSTREAM OF THE AIR FILTERS AND AHEAD OF ANY
 BRANCH CONNECTIONS IN AIR SUPPLY SYSTEMS HAVING THE
 CAPACITY GREATER THAN 2000 CUBIC FEET PER MINUTE.
  
 3) PROVIDE SPECS ON THE FABRIC DUCT. INCLUDE
 DOCUMENTATION THAT THIS PRODUCT IS LISTED AND LABELED
 IN COMPLIANCE WITH UL 2518. FMC 603.17
  
 4) THE DESIGNER OF THE MECHANICAL SYSTEM, BEAU CHANT C.
 GALLO MUST SHOW THAT THEIR DIGITAL SIGNATURE HAS BEEN
 3RD PARTY VERIFIED. FS 471/481
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  