2022-09-30 06:28:45 | 1ST REVIEW FMC |
| PERMIT: 22060301 |
| |
| CODES IN EFFECT: 2020 |
| |
| FBC- FLORIDA BUILDING CODE |
| FMC- FLORIDA MECHANICAL CODE |
| FEC- FLORIDA ENERGY CONSERVATION |
| FGC- FLORIDA FUEL GAS |
| FEX- FLORIDA EXISTING BUILDING CODE |
| FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| F.S.- FLORIDA STATUTES |
| FAC- FLORIDA ACCESSIBILITY CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) 2ND ATTEMPT: PLEASE PROVIDE THE OUTDOOR AIR |
| CALCULATIONS FOR THE OCCUPANCY FOR THESE 2 NEW RTU???S. |
| FMC 403.3.1.1 AND TABLE 403.3.1.1 |
| |
| 2) SHEET M-1 SHOWS THE DUCT SMOKE DETECTOR LOCATION AS |
| BEING IN THE RETURN DUCT. PLEASE SHOW THE DUCT SMOKE |
| DETECTORS AS BEING LOCATED IN THE SUPPLY DUCT. FMC |
| 606.2.1 |
| |
| 606.2.1 TO PREVENT THE RECIRCULATION OF DANGEROUS |
| QUANTITIES OF SMOKE, A DETECTOR APPROVED FOR AIR DUCT |
| USE SHALL BE INSTALLED ON THE SUPPLY SIDE OF |
| AIR-HANDLING SYSTEMS AS REQUIRED BY NFPA 90A, STANDARD |
| FOR THE INSTALLATION OF AIR CONDITIONING AND |
| VENTILATING SYSTEMS. SMOKE DETECTORS LISTED FOR USE IN |
| AIR DISTRIBUTION SYSTEMS SHALL BE |
| LOCATED DOWNSTREAM OF THE AIR FILTERS AND AHEAD OF ANY |
| BRANCH CONNECTIONS IN AIR SUPPLY SYSTEMS HAVING THE |
| CAPACITY GREATER THAN 2000 CUBIC FEET PER MINUTE. |
| |
| 3) PROVIDE SPECS ON THE FABRIC DUCT. INCLUDE |
| DOCUMENTATION THAT THIS PRODUCT IS LISTED AND LABELED |
| IN COMPLIANCE WITH UL 2518. FMC 603.17 |
| |
| 4) THE DESIGNER OF THE MECHANICAL SYSTEM, BEAU CHANT C. |
| GALLO MUST SHOW THAT THEIR DIGITAL SIGNATURE HAS BEEN |
| 3RD PARTY VERIFIED. FS 471/481 |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM. |
| |