Notes |
Date |
Text |
2022-06-22 08:43:00 | WHAT IS THE OCCUPANCY CLASSIFICATION OF THE TENANT | | SPACE? | | THE CONTRACT STAES THIS IS 2 NEW UNITS THAT WILL BE CUT | | INTO THE ROOF, NOT LIKE FOR LIKE CHANGE OUTS. PROVIDE A | | ROOF DRAWING SHOWING THE LOCATION OF THESE NEW RTU'S | | ALONG WITH A MECHANICAL DRAWING SHOWING THE DUCTWORK IN | | THE TENANT SPACE. | | PROVIDE THE OUTDOOR AIR CALCULATIONS FOR THESE 2 NEW | | RTU'S. FBC 107.2.1 | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | |
|