2023-06-01 17:51:20 | NEW SINGLE FAMILY RESIDENCE(R3) FOURTH BUILDING REVIEW |
| COMMENTS |
| CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| PERMIT #22060290 |
| 1001 WINDSOR AVE |
| |
| PROVISO NOTE: |
| BUILDING REVIEW MAY BE APPROVED WITH PROVISO ONCE |
| CLEAR/LEGIBLE PLANS ARE UPLOADED TO PROJECTDOX. PROVISO |
| MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER |
| THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID |
| CONFLICTS/DELAYS. REVISION FEES APPLY (EXCEPT FOR |
| PRODUCT APPROVALS DEFERRED SUBMITTAL). |
| |
| ***IMPORTANT |
| ****CONTRACTOR TO ADVICE IF PROVISO OPTION IS PREFERRED |
| AT THIS TIME OR IF RE-SUBMITTING REQUIRED INFORMATION |
| BEFORE PERMIT ISSUANCE. |
| |
| |
| 7- NEW ENERGY CALCULATIONS SUBMITTED: |
| A)FORM 401-10 WAS SUBMITTED. NEED TO SUBMIT CURRENT |
| 405-2020 FORM. |
| SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| |
| B)ITEM #5 ON PAGE 1 SPECIFIES WORST CASE SCENARIO. |
| ENERGY CALCULATIONS NEED TO BE SITE SPECIFIC AS |
| REQUIRED BY SEC. R405.4.2.1 (4) FBC- ENERGY |
| CONSERVATION. |
| REVISE AS REQUIRED. |
| |
| C)CONCRETE BLOCK INSULATION R-VALUE DOESN???T MATCH |
| R-VALUE SPECIFIED ON TYPICAL WALL SECTION. REVISE AS |
| REQUIRED TO MATCH. |
| SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| |
| D)REVISE SPACE INFORMATION ON PAGE 2. NUMBER OF |
| OCCUPANTS CAN NOT BE 3.5. NEED TO ROUND UP THE NUMBER. |
| SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| |
| E)REVISE DOOR ORIENTIN ON PAGE 3. ENTRY DOO IS ON THE |
| EAST SIDE. |
| SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| |
| F)REVISE WINDOWS INFORMATION TO MATCH PLANS. REVISE |
| WINDOWS ORIENTATION, WINDOWS FRAME TYPE (ALUMINUM, NOT |
| VINYL), WINDOWS AREA AND WINDOWS OVERHANG DEPTH AND |
| SEPARATION TO MATCH PLANS. ALSO, THERE IS NOT GLASS |
| BLOCK ON PLANS. |
| SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| |
| |
| 8- ALL RESUBMITTED PLANS ARE NOT LEGIBLE. NEED TO |
| UPLOAD CLEAR AND LEGIBLE DRAWINGS. SEC. 107.2.1 CITY |
| AMENDMENTS. SEC. 107.2.1.3 CITY AMENDMENTS. |
| |
| RESPONSE: |
| PLANS ARE STILL NOT LEGIBLE. |
| |
| 9- ENGINEER TO REVISE SITE DRAINAGE PLAN ON SHEET 8. |
| THE PROPOSED GRADE AT THE SWALE AREA IS HIGHER THAN THE |
| ADJACENT GRADE. ALSO, IT DOESN'T MATCH SECTION DETAILS |
| A-A, B-B AND C-C. |
| ACCORDING TO SECTION DETAILS A-A, B-B AND C-C THE GRADE |
| IS HIGHER AT THE PERIMETER OF THE LOT. ENGINEER OF |
| RECORD TO PROVIDE DETAILS AND SPECIFICATIONS SHOWING |
| HOW THE RAISED GRADE IS SUPPORTED. IF RETAINING WALLS |
| ARE REQUIRED, THEN SEPARATE PERMIT IS REQUIRED. SEC. |
| 105.1 CITY AMENDMENTS, SEC. 105.2.5 CITY AMENDMENTS. |
| SEC. R401.3 FC-RESIDENTIAL. |
| NOTE: DRAINAGE PLAN TO SHOW THE EXISTING AND PROPOSED |
| GRADE ELEVATIONS SHOWING HOW KEEPING WATER AWAY FROM |
| ADJACENT PROPERTIES. |
| |
| RESPONSE: |
| UNABLE TO READ THE PLANS. |
| |
| WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND |
| HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE |
| REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |