2023-03-03 17:37:27NEW SINGLE FAMILY RESIDENCE (R3) THIRD BUILDING REVIEW
 COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #22060290
 1001 WINDSOR AVE
  
 7- ENERGY CALCULATIONS SUBMITTED:
 PREVIOUS COMMENT:
 A) NEED TO COMPLETE THE "INSTALLED" INFORMATION ON PAGE
 1 AS REQUIRED BY THE GENERAL INSTRUCTIONS ON SAME
 SHEET. SEC. R101.5.1.1.1 FBC-ENERGY CONSERVATION.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
 NOTE: IF ALL OF THE VALUES LISTED UNDER CLIMATE ZONE 1
 ARE NOT INSTALLED, THEN THIS PRESCRIPTIVE FORM CANNOT
 BE USED. SEE SCOPE INFORMATION ON TOP OF GENERAL
 INSTRUCTIONS OF FORM 402-2020 SUBMITTED.
  
 PREVIOUS COMMENT:
 B)NEED TO COMPLETE THE "INSTALLED EFFICIENCY LEVEL"
 INFORMATION ON PAGE 2 AS REQUIRED BY THE NOTE ON TOP OF
 SAME SHEET. SPECIFY THE DUCT R-VALUE. SEC. R101.5.1.1.1
 FBC-ENERGY CONSERVATION.
  
 RESPONSE:
 R-VALUE SPECIFIED IS INCORRECT. DUCTS R-VALUE IN
 UNCONDITIONED ATTICS IS R-8 NOT R-6.
 ALSO, SPECIFY LOCATION OF AIR HANDLER.
  
 PREVIOUS COMMENT:
 8- ALL RESUBMITTED PLANS ARE NOT LEGIBLE. NEED TO
 UPLOAD CLEAR AND LEGIBLE DRAWINGS. SEC. 107.2.1 CITY
 AMENDMENTS. SEC. 107.2.1.3 CITY AMENDMENTS.
  
 RESPONSE:
 PLANS NEED TO BE CLEAR TO BE REVIEWED AND STAMPED.
 THOSE WILL BE THE OFFICIAL APPROVED PLANS. IF THE
 ORIGINALS RE NOT CLEAR, THEN THE PLANS WILL NOT BE
 LEGIBLE WHEN PRINTING FOR THE JOB SITE EITHER.
 MECHANICAL REVIEWER HAS COMMENTS REGARDING THIS ISSUE
 ALSO.
 WE NEED LEGIBLE COPIES FOR RECORDS MANAGEMENT. SEC.
 107.2.1.3 CITY AMENDMENTS.
  
 PREVIOUS COMMENT:
 9- ENGINEER TO REVISE SITE DRAINAGE PLAN ON SHEET 8.
 THE PROPOSED GRADE AT THE SWALE AREA IS HIGHER THAN THE
 ADJACENT GRADE. ALSO, IT DOESN'T MATCH SECTION DETAILS
 A-A, B-B AND C-C.
 ACCORDING TO SECTION DETAILS A-A, B-B AND C-C THE GRADE
 IS HIGHER AT THE PERIMETER OF THE LOT. ENGINEER OF
 RECORD TO PROVIDE DETAILS AND SPECIFICATIONS SHOWING
 HOW THE RAISED GRADE IS SUPPORTED. IF RETAINING WALLS
 ARE REQUIRED, THEN SEPARATE PERMIT IS REQUIRED. SEC.
 105.1 CITY AMENDMENTS, SEC. 105.2.5 CITY AMENDMENTS.
 SEC. R401.3 FC-RESIDENTIAL.
 NOTE: DRAINAGE PLAN TO SHOW THE EXISTING AND PROPOSED
 GRADE ELEVATIONS SHOWING HOW KEEPING WATER AWAY FROM
 ADJACENT PROPERTIES.
  
 RESPONSE:
 DRAINAGE PLAN IS NOT LEGIBLE. UNABLE TO REVIEW.
 ALSO, ENGINEER DOESN'T SHOW HOW RAISING THE GRADE AT
 THE PERIMETER OF THE LOT. RETAINING WALL REQUIRED?
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND
 HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE
 REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  