Date |
Text |
2023-01-25 14:23:42 | NEW SINGLE FAMILY RESIDENCE (R3) SECOND BUILDING REVIEW |
| COMMENTS |
| CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| PERMIT #22060290 1001 WINDSOR AVE |
| |
| ARCHITECTS-ENGINEERS |
| FLORIDA STATUTE 553.80(2)(B): |
| ARCHITECTS WITH RESPECT TO EVALUATION OF DESIGN |
| PROFESSIONALS DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT |
| NECESSARY, IN ORDER TO ENFORCE COMPLIANCE WITH THE |
| FLORIDA BUILDING CODE AND ISSUE A PERMIT, TO REJECT |
| DESIGN DOCUMENTS REQUIRED BY THE CODE THREE OR MORE |
| TIMES FOR FAILURE TO CORRECT A CODE VIOLATION |
| SPECIFICALLY AND CONTINUOUSLY NOTED IN EACH REJECTION, |
| INCLUDING, BUT NOT LIMITED TO, EGRESS, FIRE PROTECTION, |
| STRUCTURAL STABILITY, ENERGY, ACCESSIBILITY, LIGHTING, |
| VENTILATION, ELECTRICAL, MECHANICAL, PLUMBING, AND GAS |
| SYSTEMS, OR OTHER REQUIREMENTS IDENTIFIED BY RULE OF |
| THE FLORIDA BUILDING COMMISSION ADOPTED PURSUANT TO |
| CHAPTER 120, THE LOCAL GOVERNMENT SHALL IMPOSE, EACH |
| TIME AFTER THE THIRD SUCH REVIEW THE PLANS ARE REJECTED |
| FOR THAT CODE VIOLATION, A FEE OF FOUR TIMES THE AMOUNT |
| OF THE PROPORTION OF THE PERMIT FEE ATTRIBUTED TO PLANS |
| REVIEW |
| |
| |
| ORIGINAL COMMENT: |
| 1- BEDROOM #3 AND BEDROOM #4. THE SPECIFIED WINDOW SIZE |
| DOESN'T SEEM TO COMPLY WITH EGRESS REQUIREMENTS OF SEC. |
| R310.2.1 FBC-RESIDENTIAL. TYPICALLY, 50-3/8" SINGLE |
| HUNG WINDOW DOESN'T PROVIDE THE REQUIRED 24" CLEAR |
| HEIGHT. REVISE SIZE OR PROVIDE MANUFACTURER'S |
| SPECIFICATIONS SHOWING COMPLIANCE WITH ALL THE EGRESS |
| CLEAR OPENINGS. |
| |
| RESPONSE: |
| WINDOW SIZE WAS NOT REVISED. NEED TO REVISE. TYPICALLY, |
| 37" X 63" WINDOWS AS SPECIFIED FOR BEDROOM #2 ARE THE |
| ONES COMPLYING WITH THE EGRESS REQUIREMENTS. REVISE AS |
| REQUIRED. |
| |
| ORIGINAL COMMENT: |
| 2- REVISE ROOF SHEATHING NAILING SPECIFICATIONS TO |
| COMPLY WITH NEW 2020 FBC-RESIDENTIAL NAILING SPACING |
| SPECIFICATIONS. ROOF SHEATHING NEEDS TO BE NAILED AT 4 |
| INCHES O.C. IN THE FIELD AND EDGES AS REQUIRED BY SEC. |
| R803.2.3.1 AND TABLE R803.2.3.1 FBC-RESIDENTIAL. |
| NOTE: REVISE SPECIFICATIONS OR PROVIDE CALCULATIONS |
| SHOWING THAT SPECIFIED NAIL TYPE AND SPACING MATCHES OR |
| EXCEEDS TABLE R803.2.3.1 FBC-RESIDENTIAL MINIMUM |
| REQUIREMENTS. |
| REVISE NOTE "C" ON PLYWOOD ROOF SHEATHING NOTES AND |
| NOTE #9 ON ROOF PLAN NOTES ON SHEET GN. TYPICAL WALL |
| SECTION ON SHEET 4. |
| |
| RESPONSE: |
| ROOF SHEATHING SPECIFICATIONS ON TYPICAL WALL SECTION |
| ON SHEET 4 WAS NOT REVISED TO SHOW COMPLIANCE. NEED TO |
| REVISE AS REQUIRED. |
| |
| ORIGINAL COMMENT: |
| 3- ATTIC VENTILATION SPECIFIED ON ATTIC VENTILATION |
| CALCULATION ON SHEET 1 AND VENTED ALUMINUM SOFFIT |
| SPECIFICATION SHOWN ON THE TYPICAL WALL SECTION ON |
| SHEET 4 DON'T MATCH. REVISE AS REQUIRED TO MATCH. SEC. |
| R806 FBC-RESIDENTIAL. |
| |
| RESPONSE: |
| REPEAT COMMENT. NOT ADDRESSED. |
| |
| 4- OK. |
| 5- OK. |
| 6- OK. |
| |
| 7- ENERGY CALCULATIONS SUBMITTED: |
| ORIGINAL COMMENT: |
| A) NEED TO COMPLETE THE "INSTALLED" INFORMATION ON PAGE |
| 1 AS REQUIRED BY THE GENERAL INSTRUCTIONS ON SAME |
| SHEET. SEC. R101.5.1.1.1 FBC-ENERGY CONSERVATION. |
| |
| RESPONSE: |
| REPEAT COMMENT. NOT ADDRESSED. |
| |
| ORIGINAL COMMENT: |
| B)NEED TO COMPLETE THE "INSTALLED EFFICIENCY LEVEL" |
| INFORMATION ON PAGE 2 AS REQUIRED BY THE NOTE ON TOP OF |
| SAME SHEET. SPECIFY THE DUCT R-VALUE. SEC. R101.5.1.1.1 |
| FBC-ENERGY CONSERVATION. |
| |
| RESPONSE: |
| R-VALUE SPECIFIED IS INCORRECT. DUCTS DIAMETER IS |
| GREATER THAN 3 IN. |
| ALSO, SPECIFY LOCATION OF AIR HANDLER. |
| |
| C)OK. |
| D)OK. |
| E)OK. |
| |
| NEW COMMENT BASED ON INFORMATION SUBMITTED: |
| 8- ALL RESUBMITTED PLANS ARE NOT LEGIBLE. NEED TO |
| UPLOAD CLEAR AND LEGIBLE DRAWINGS. SEC. 107.2.1 CITY |
| AMENDMENTS. SEC. 107.2.1.3 CITY AMENDMENTS. |
| |
| 9- ENGINEER TO REVISE SITE DRAINAGE PLAN ON SHEET 8. |
| THE PROPOSED GRADE AT THE SWALE AREA IS HIGHER THAN THE |
| ADJACENT GRADE. ALSO, IT DOESN'T MATCH SECTION DETAILS |
| A-A, B-B AND C-C. |
| ACCORDING TO SECTION DETAILS A-A, B-B AND C-C THE GRADE |
| IS HIGHER AT THE PERIMETER OF THE LOT. ENGINEER OF |
| RECORD TO PROVIDE DETAILS AND SPECIFICATIONS SHOWING |
| HOW THE RAISED GRADE IS SUPPORTED. IF RETAINING WALLS |
| ARE REQUIRED, THEN SEPARATE PERMIT IS REQUIRED. SEC. |
| 105.1 CITY AMENDMENTS, SEC. 105.2.5 CITY AMENDMENTS. |
| SEC. R401.3 FC-RESIDENTIAL. |
| NOTE: DRAINAGE PLAN TO SHOW THE EXISTING AND PROPOSED |
| GRADE ELEVATIONS SHOWING HOW KEEPING WATER AWAY FROM |
| ADJACENT PROPERTIES. |
| |
| WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND |
| HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE |
| REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| QUESTIONS REGARDING THESE COMMENTS, |
| JULIO GOMEZ |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| DEVELOPMENT SERVICES DEPARTMENT |
| BUILDING DIVISION |
| (561)805-6712 |
| [email protected] |
| |
| |