Plan Review Notes
Plan Review Notes For Permit 22060290
Permit Number 22060290
Review Stop B
Sequence Number 2
Notes
Date Text
2023-01-25 14:23:42NEW SINGLE FAMILY RESIDENCE (R3) SECOND BUILDING REVIEW
 COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #22060290 1001 WINDSOR AVE
  
 ARCHITECTS-ENGINEERS
 FLORIDA STATUTE 553.80(2)(B):
 ARCHITECTS WITH RESPECT TO EVALUATION OF DESIGN
 PROFESSIONALS DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT
 NECESSARY, IN ORDER TO ENFORCE COMPLIANCE WITH THE
 FLORIDA BUILDING CODE AND ISSUE A PERMIT, TO REJECT
 DESIGN DOCUMENTS REQUIRED BY THE CODE THREE OR MORE
 TIMES FOR FAILURE TO CORRECT A CODE VIOLATION
 SPECIFICALLY AND CONTINUOUSLY NOTED IN EACH REJECTION,
 INCLUDING, BUT NOT LIMITED TO, EGRESS, FIRE PROTECTION,
 STRUCTURAL STABILITY, ENERGY, ACCESSIBILITY, LIGHTING,
 VENTILATION, ELECTRICAL, MECHANICAL, PLUMBING, AND GAS
 SYSTEMS, OR OTHER REQUIREMENTS IDENTIFIED BY RULE OF
 THE FLORIDA BUILDING COMMISSION ADOPTED PURSUANT TO
 CHAPTER 120, THE LOCAL GOVERNMENT SHALL IMPOSE, EACH
 TIME AFTER THE THIRD SUCH REVIEW THE PLANS ARE REJECTED
 FOR THAT CODE VIOLATION, A FEE OF FOUR TIMES THE AMOUNT
 OF THE PROPORTION OF THE PERMIT FEE ATTRIBUTED TO PLANS
 REVIEW
  
  
 ORIGINAL COMMENT:
 1- BEDROOM #3 AND BEDROOM #4. THE SPECIFIED WINDOW SIZE
 DOESN'T SEEM TO COMPLY WITH EGRESS REQUIREMENTS OF SEC.
 R310.2.1 FBC-RESIDENTIAL. TYPICALLY, 50-3/8" SINGLE
 HUNG WINDOW DOESN'T PROVIDE THE REQUIRED 24" CLEAR
 HEIGHT. REVISE SIZE OR PROVIDE MANUFACTURER'S
 SPECIFICATIONS SHOWING COMPLIANCE WITH ALL THE EGRESS
 CLEAR OPENINGS.
  
 RESPONSE:
 WINDOW SIZE WAS NOT REVISED. NEED TO REVISE. TYPICALLY,
 37" X 63" WINDOWS AS SPECIFIED FOR BEDROOM #2 ARE THE
 ONES COMPLYING WITH THE EGRESS REQUIREMENTS. REVISE AS
 REQUIRED.
  
 ORIGINAL COMMENT:
 2- REVISE ROOF SHEATHING NAILING SPECIFICATIONS TO
 COMPLY WITH NEW 2020 FBC-RESIDENTIAL NAILING SPACING
 SPECIFICATIONS. ROOF SHEATHING NEEDS TO BE NAILED AT 4
 INCHES O.C. IN THE FIELD AND EDGES AS REQUIRED BY SEC.
 R803.2.3.1 AND TABLE R803.2.3.1 FBC-RESIDENTIAL.
 NOTE: REVISE SPECIFICATIONS OR PROVIDE CALCULATIONS
 SHOWING THAT SPECIFIED NAIL TYPE AND SPACING MATCHES OR
 EXCEEDS TABLE R803.2.3.1 FBC-RESIDENTIAL MINIMUM
 REQUIREMENTS.
 REVISE NOTE "C" ON PLYWOOD ROOF SHEATHING NOTES AND
 NOTE #9 ON ROOF PLAN NOTES ON SHEET GN. TYPICAL WALL
 SECTION ON SHEET 4.
  
 RESPONSE:
 ROOF SHEATHING SPECIFICATIONS ON TYPICAL WALL SECTION
 ON SHEET 4 WAS NOT REVISED TO SHOW COMPLIANCE. NEED TO
 REVISE AS REQUIRED.
  
 ORIGINAL COMMENT:
 3- ATTIC VENTILATION SPECIFIED ON ATTIC VENTILATION
 CALCULATION ON SHEET 1 AND VENTED ALUMINUM SOFFIT
 SPECIFICATION SHOWN ON THE TYPICAL WALL SECTION ON
 SHEET 4 DON'T MATCH. REVISE AS REQUIRED TO MATCH. SEC.
 R806 FBC-RESIDENTIAL.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 4- OK.
 5- OK.
 6- OK.
  
 7- ENERGY CALCULATIONS SUBMITTED:
 ORIGINAL COMMENT:
 A) NEED TO COMPLETE THE "INSTALLED" INFORMATION ON PAGE
 1 AS REQUIRED BY THE GENERAL INSTRUCTIONS ON SAME
 SHEET. SEC. R101.5.1.1.1 FBC-ENERGY CONSERVATION.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 B)NEED TO COMPLETE THE "INSTALLED EFFICIENCY LEVEL"
 INFORMATION ON PAGE 2 AS REQUIRED BY THE NOTE ON TOP OF
 SAME SHEET. SPECIFY THE DUCT R-VALUE. SEC. R101.5.1.1.1
 FBC-ENERGY CONSERVATION.
  
 RESPONSE:
 R-VALUE SPECIFIED IS INCORRECT. DUCTS DIAMETER IS
 GREATER THAN 3 IN.
 ALSO, SPECIFY LOCATION OF AIR HANDLER.
  
 C)OK.
 D)OK.
 E)OK.
  
 NEW COMMENT BASED ON INFORMATION SUBMITTED:
 8- ALL RESUBMITTED PLANS ARE NOT LEGIBLE. NEED TO
 UPLOAD CLEAR AND LEGIBLE DRAWINGS. SEC. 107.2.1 CITY
 AMENDMENTS. SEC. 107.2.1.3 CITY AMENDMENTS.
  
 9- ENGINEER TO REVISE SITE DRAINAGE PLAN ON SHEET 8.
 THE PROPOSED GRADE AT THE SWALE AREA IS HIGHER THAN THE
 ADJACENT GRADE. ALSO, IT DOESN'T MATCH SECTION DETAILS
 A-A, B-B AND C-C.
 ACCORDING TO SECTION DETAILS A-A, B-B AND C-C THE GRADE
 IS HIGHER AT THE PERIMETER OF THE LOT. ENGINEER OF
 RECORD TO PROVIDE DETAILS AND SPECIFICATIONS SHOWING
 HOW THE RAISED GRADE IS SUPPORTED. IF RETAINING WALLS
 ARE REQUIRED, THEN SEPARATE PERMIT IS REQUIRED. SEC.
 105.1 CITY AMENDMENTS, SEC. 105.2.5 CITY AMENDMENTS.
 SEC. R401.3 FC-RESIDENTIAL.
 NOTE: DRAINAGE PLAN TO SHOW THE EXISTING AND PROPOSED
 GRADE ELEVATIONS SHOWING HOW KEEPING WATER AWAY FROM
 ADJACENT PROPERTIES.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND
 HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE
 REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved