Plan Review Notes
Plan Review Notes For Permit 22060290
Permit Number 22060290
Review Stop B
Sequence Number 1
Notes
Date Text
2022-08-01 10:18:17NEW SINGLE FAMILY RESIDENCE (R3) BUILDING REVIEW
 COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #22060290 1001 WINDSOR AVE
  
 1- BEDROOM #3 AND BEDROOM #4. THE SPECIFIED WINDOW SIZE
 DOESN'T SEEM TO COMPLY WITH EGRESS REQUIREMENTS OF SEC.
 R310.2.1 FBC-RESIDENTIAL. TYPICALLY, 50-3/8" SINGLE
 HUNG WINDOW DOESN'T PROVIDE THE REQUIRED 24" CLEAR
 HEIGHT. REVISE SIZE OR PROVIDE MANUFACTURER'S
 SPECIFICATIONS SHOWING COMPLIANCE WITH ALL THE EGRESS
 CLEAR OPENINGS.
  
 2- REVISE ROOF SHEATHING NAILING SPECIFICATIONS TO
 COMPLY WITH NEW 2020 FBC-RESIDENTIAL NAILING SPACING
 SPECIFICATIONS. ROOF SHEATHING NEEDS TO BE NAILED AT 4
 INCHES O.C. IN THE FIELD AND EDGES AS REQUIRED BY SEC.
 R803.2.3.1 AND TABLE R803.2.3.1 FBC-RESIDENTIAL.
 NOTE: REVISE SPECIFICATIONS OR PROVIDE CALCULATIONS
 SHOWING THAT SPECIFIED NAIL TYPE AND SPACING MATCHES OR
 EXCEEDS TABLE R803.2.3.1 FBC-RESIDENTIAL MINIMUM
 REQUIREMENTS.
 REVISE NOTE "C" ON PLYWOOD ROOF SHEATHING NOTES AND
 NOTE #9 ON ROOF PLAN NOTES ON SHEET GN. TYPICAL WALL
 SECTION ON SHEET 4.
  
 3- ATTIC VENTILATION SPECIFIED ON ATTIC VENTILATION
 CALCULATION ON SHEET 1 AND VENTED ALUMINUM SOFFIT
 SPECIFICATION SHOWN ON THE TYPICAL WALL SECTION ON
 SHEET 4 DON'T MATCH. REVISE AS REQUIRED TO MATCH. SEC.
 R806 FBC-RESIDENTIAL.
  
 4- NORTH ARROW ORIENTATION SHOWN ON ALL PLANS SUBMITTED
 IS INCORRECT. SEE SURVEY AND REVISE AS REQUIRED. SEC.
 107.2.1 CITY AMENDMENTS.
  
 5- PRODUCT APPROVALS
 PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC 61G20-3.001
 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW
 PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL
 PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY
 DESIGNER OF RECORD PRIOR TO SUBMITTAL):
  
 A)VENTED ALUMINUM SOFFIT SPECIFIED ON THE TYPICAL WALL
 SECTION.
  
 6- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 7- ENERGY CALCULATIONS SUBMITTED:
 A) NEED TO COMPLETE THE "INSTALLED" INFORMATION ON PAGE
 1 AS REQUIRED BY THE GENERAL INSTRUCTIONS ON SAME
 SHEET. SEC. R101.5.1.1.1 FBC-ENERGY CONSERVATION.
  
 B)NEED TO COMPLETE THE "INSTALLED EFFICIENCY LEVEL"
 INFORMATION ON PAGE 2 AS REQUIRED BY THE NOTE ON TOP OF
 SAME SHEET. SPECIFY THE DUCT R-VALUE. SEC. R101.5.1.1.1
 FBC-ENERGY CONSERVATION.
  
 C)DUCT TESTING IS REQUIRED. REVISE INFORMATION ON PAGE
 2. SEC. R101.5.1.1.1 FBC-ENERGY CONSERVATION.
  
 D)THERE IS NOT PTAC INSTALLED IN THIS HOUSE. REVISE
 INFORMATION SHOWN ON PAGE 2. SEC. R101.5.1.1.1
 FBC-ENERGY CONSERVATION.
  
 E)WATER HEATER INFORMATION ON PAGE 2 DOESN'T MATCH
 PLANS. SEC. R101.5.1.1.1 FBC-ENERGY CONSERVATION.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND
 HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE
 REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  