Plan Review Notes
Plan Review Notes For Permit 22060245
Permit Number 22060245
Review Stop P
Sequence Number 1
Notes
Date Text
2022-06-15 12:11:591ST REVIEW FBC-2020 RES. PLUMBING
 PERMIT- 22060245
 6/15/2022
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P-4: PROVIDE THE POOL PUMP CURVE ON THE PLAN
 SHEET- SECS. 4.4.9, 4.4.9.1 ANSI/APSP/ICC-7 & R4501.7.2
 & R4501.7.3 FBC RES.2
  
 2) P-3 & P-4: IF AN AUTOFILL IS TO BE INSTALLED, PLEASE
 SHOW THE LOCATIONS OF THE DEVICE AND THE REQUIRED
 BACKFLOW PREVENTER TO PROTECT THE POTABLE WATER SYSTEM-
 SEC. R4501.9 & P2902.3 FBC RES. PLEASE INDICATE THE
 TYPE OF BACKFLOW PREVENTER TO BE INSTALLED- TABLE
 P2902.3 FBC RES.
  
 3) PLEASE NOTE A RPZ BACKFLOW PREVENTER IS REQUIRED AT
 THE WATER METER TO PROTECT THE POTABLE WATER SERVICE-
 SEC. C & D WPB UTILITIES CROSS-CONNECTION MANUAL. THE
 DEVICE SHALL BE INSTALLED UNDER A SEPARATE PERMIT- SEC.
 105.1 WPB.
  
 4) SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE HAYWARD
 ANTI-ENTRAPMENT CHANNEL DRAIN ASSEMBLY INCLUDING
 SUCTION OUTLET COVER AND FRAME- SEC. R4501.6.2 &
 R4501.6.6 FBC RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  