Notes |
Date |
Text |
2022-06-15 12:11:59 | 1ST REVIEW FBC-2020 RES. PLUMBING | | PERMIT- 22060245 | | 6/15/2022 | | | | CODES IN EFFECT: | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | 2020 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) SHEET P-4: PROVIDE THE POOL PUMP CURVE ON THE PLAN | | SHEET- SECS. 4.4.9, 4.4.9.1 ANSI/APSP/ICC-7 & R4501.7.2 | | & R4501.7.3 FBC RES.2 | | | | 2) P-3 & P-4: IF AN AUTOFILL IS TO BE INSTALLED, PLEASE | | SHOW THE LOCATIONS OF THE DEVICE AND THE REQUIRED | | BACKFLOW PREVENTER TO PROTECT THE POTABLE WATER SYSTEM- | | SEC. R4501.9 & P2902.3 FBC RES. PLEASE INDICATE THE | | TYPE OF BACKFLOW PREVENTER TO BE INSTALLED- TABLE | | P2902.3 FBC RES. | | | | 3) PLEASE NOTE A RPZ BACKFLOW PREVENTER IS REQUIRED AT | | THE WATER METER TO PROTECT THE POTABLE WATER SERVICE- | | SEC. C & D WPB UTILITIES CROSS-CONNECTION MANUAL. THE | | DEVICE SHALL BE INSTALLED UNDER A SEPARATE PERMIT- SEC. | | 105.1 WPB. | | | | 4) SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE HAYWARD | | ANTI-ENTRAPMENT CHANNEL DRAIN ASSEMBLY INCLUDING | | SUCTION OUTLET COVER AND FRAME- SEC. R4501.6.2 & | | R4501.6.6 FBC RES. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. | | | | CHRISTOPHER L. COLE | | MECHANICAL/PLUMBING PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|