Plan Review Notes
Plan Review Notes For Permit 22060238
Permit Number 22060238
Review Stop G
Sequence Number 1
Notes
Date Text
2023-01-31 08:42:271ST REVIEW FBC-2020 RES. GAS
 PERMIT- 22060238
 1/31/2023
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE A FLOOR OR SITE PLAN DRAWING SHOWING
 THE LOCATIONS OF THE METER AND THE NEW GAS APPLIANCES.
 FOR EXTERIOR APPLIANCES PLEASE INCLUDE CLEARANCE
 DISTANCE MEASUREMENTS FROM EXHAUST OUTLETS TO OPERABLE
 DOORS AND WINDOWS AND AIR INTAKES INTO THE BUILDING-
 SEC. 107.3.5.3 (13) WPB AND SEC. G2427.8 FBC RES.
  
 2) GAS RISER: LABEL THE POOL HEATER AS FUTURE AND SHOW
 A GAS-TIGHT CAP WILL BE INSTALLED- SEC. G2415.15 FBC
 RES. THE WPB BUILDING DEPT. REQUIRES A SEPARATE PERMIT
 FOR POOL HEATERS- SEC. 105.1 & 107.1 WPB.
  
 3) GAS RISER: THE PRINTED NAME AND SIGNATURE OF THE FL.
 LICENSED CONTRACTOR OR QUALIFIER SHALL BE ON THE
 DRAWING- SEC. 107.2.1 WPB.
  
 4) PROVIDE COMBUSTION CALCULATIONS FOR THE COOKTOP. IF
 USING INDOOR AIR AND THE STANDARD METHOD PER SECS.
 G2407.5 & G2407.5.2 THE MINIMUM REQUIRED VOLUME SHALL
 BE 50 CUBIC FEET PER 1,000 BTU OF THE APPLIANCE INPUT
 RATING OR 3120 CU. FT.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  