Plan Review Notes
Plan Review Notes For Permit 22060054
Permit Number 22060054
Review Stop M
Sequence Number 1
Notes
Date Text
2022-06-24 06:31:171ST REVIEW FMC
 PERMIT: 22060054
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE THE ENERGY CALCULATIONS FOR THIS PROJECT,
 MAKE SURE TO INCLUDE THE GARAGE IN THESE CALCULATIONS.
 FEC 101.5.1.1.2
  
 2) PROVIDE THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS. FEC R403.7
  
 3) THERE IS NO 2ND FLOOR MECHANICAL PLAN IN THIS
 SUBMITTAL.
  
 4) PROVIDE THE CFM?S OF THE KITCHEN HOOD EXHAUST ON THE
 DRAWING. FRC M1503
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  