Plan Review Notes For Permit 22060054 |
Permit Number |
22060054 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2022-06-24 06:31:17 | 1ST REVIEW FMC | | PERMIT: 22060054 | | | | CODES IN EFFECT: 2020 | | | | FBC- FLORIDA BUILDING CODE | | FMC- FLORIDA MECHANICAL CODE | | FEC- FLORIDA ENERGY CONSERVATION | | FGC- FLORIDA FUEL GAS | | FEX- FLORIDA EXISTING BUILDING CODE | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | F.S.- FLORIDA STATUTES | | FAC- FLORIDA ACCESSIBILITY CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) PROVIDE THE ENERGY CALCULATIONS FOR THIS PROJECT, | | MAKE SURE TO INCLUDE THE GARAGE IN THESE CALCULATIONS. | | FEC 101.5.1.1.2 | | | | 2) PROVIDE THE MECHANICAL EQUIPMENT SIZING | | CALCULATIONS. FEC R403.7 | | | | 3) THERE IS NO 2ND FLOOR MECHANICAL PLAN IN THIS | | SUBMITTAL. | | | | 4) PROVIDE THE CFM?S OF THE KITCHEN HOOD EXHAUST ON THE | | DRAWING. FRC M1503 | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM. | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | |
|