Plan Review Notes For Permit 22060009 |
Permit Number |
22060009 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2022-06-23 12:47:04 | ELECTRIC REVIEW FAILED | | | | 1) VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS | | LOW. PROVIDE A BREAKDOWN OF ALL MATERIALS AND LABOR, | | OR, AT YOUR DISCRETION, PROVIDE A SIGNED CONTRACTOR OR | | PROVIDE A REASONABLE VALUE. WPB F.B.C. 109.3 | | 2) PLEASE DETAIL NEW ELECTRIC WORK TO BE IN COMPLIANCE | | WITH THE FOLLOWING, | | NEC 210.8 GFCI PROTECTION, | | NEC 210.12 AND NEC 406.4 ARC-FAULT PROTECTION, | | NEC 210.52 RECEPTACLE SPACING, | | NEC 406.12 AND NEC 406.4(D)(5) TAMPER RESISTANT | | RECEPTACLES, | | NEC 250.140 GROUNDING | | SMOKE/CARBON ALARMS AS PER FBC R 314 | | 3) SEE SIGNATURE REVIEW | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. | | | | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | BUILDING CODE 2020 7TH ED. | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | 7TH EDITION | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | 7TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | V/R, | | | | MICHAEL PETERSON | | ELECTRICAL PLANS EXAMINER | | [email protected] | | 561-805-6746 | | |
|