Plan Review Notes For Permit 22051508 |
Permit Number |
22051508 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2022-06-15 13:23:02 | ELECTRIC REVIEW FAILED | | 1)PLEASE PROVIDE AN ELECTRIC FLOOR PLAN DETAILING ALL | | ELECTRIC WORK REMOVED, REPLACED, MODIFIED OR ADDED. | | ENSURE TO COMPLY WITH ALL APPLICABLE NEC AND FB CODES, | | INCLUDING BUT NOT LIMITED TO THE FOLLOWING: NEC 210.8 | | GFCI PROTECTION, NEC 210.12 AND NEC 406.4 ARC-FAULT | | PROTECTION, NEC 220.52 RECEPTACLE SPACING, NEC 406.12 | | AND NEC 406.4(D)(5) TAMPER RESISTANT RECEPTACLES, NEC | | 250.140 GROUNDING AND SMOKE/CARBON ALARMS AS PER FBC | | 553.883. | | FBC 107.2 | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. | | | | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | BUILDING CODE 2020 7TH ED. | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | 7TH EDITION | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | 7TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | V/R, | | | | MICHAEL PETERSON | | ELECTRICAL PLANS EXAMINER | | [email protected] | | 561-805-6746 | | |
|