Plan Review Notes
Plan Review Notes For Permit 22051385
Permit Number 22051385
Review Stop P
Sequence Number 1
Notes
Date Text
2022-06-02 14:18:571ST REVIEW FBC-2020 PLUMBING
 PERMIIT- 22051385
 6/2/2022
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE A PLUMBING PIPING LAYOUT PLAN THAT
 SHOWS THE LOCATIONS OF NEW SANITARY DRAIN AND VENT
 PIPING, LOCATIONS OF THE EXISTING STACKS SHOWN IN THE
 ISOMETRIC DRAWING ON SHEET 3, AND THE LOCATIONS OF NEW
 WATER SUPPLY PIPING- SEC. 107.2.1 WPB.
  
 2) SHEET 2: THE PLAN INDICATES THE NEW FIRST FLOOR
 POWDER ROOM IS BEING DESIGNED TO MEET SPECIFICATION B
 PER THE FAIR HOUSING DESIGN ACT. PLEASE REFER TO PAGE
 7.35 OF THE FAIR HOUSING DESIGN ACT MANUAL AND PROVIDE
 ENLARGED FLOOR PLAN AND ELEVATION DRAWINGS SHOWING THE
 FOLLOWING DETAILS:
 A) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE
 WATER CLOSET- PAGE 7.48
 B) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 LAVATORY. THE CLEAR FLOOR SPACE SHALL BE OUTSIDE THE
 SWING OF THE DOOR- PAGE 7.38.
 C) TOILET GRAB BAR REINFORCEMENT LOCATIONS- PAGES 6.3-
 6.5
  
 3) SHEET 2: SHOW THE CLEAR FLOOR SPACE DIAGRAMS WITH
 DIMENSIONS FOR THE KITCHEN SINK, DISHWASHER, AND BAR
 SINK- PAGES 7.2- 7.6 FAIR HOUSING DESIGN ACT MANUAL.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  