Plan Review Notes For Permit 22051342 |
Permit Number |
22051342 |
|
Review Stop |
G |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2022-08-25 07:31:27 | 2ND GAS REVIEW | | | | V7 FPC - 2020 FLORIDA PLUMBING CODE | | V7 FGC - 2020 FLORIDA FUEL GAS | | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE | | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE | | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE | | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION | | 2021 F.S. - 2021 FLORIDA STATUTES | | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE | | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE | | FBC CHAPTER 1 | | | | THIS PLAN WAS REVIEWED FOR CODE | | | | 1. NEW COMMENT - 2020 FRC G2413 (402) - PER THE TABLE | | REFERENCED, THE PRESSURE AND THE LONGEST RUN, YOU ARE | | UNDERSIZED. 1" CSST AT 90 FT CAN ONLY CARRY 311,000 | | BTU, AND YOU HAVE 440,000. CHECK THE PRESSURE PROVIDED | | AND MAKE SURE YOU ARE USING THE CORRECT TABLE. IF | | NECESSARY, ADJUST SIZES. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM. | | | | | | RYAN W. BROWN | | CHIEF PLUMBING INSPECTOR | | OFFICE: 561-805-6692 | | CELL: 561-517-4293 | | EMAIL: [email protected] | | |
|