2022-07-27 13:31:41 | AUDITORIUM RENOVATION |
| REVIEWED BY ROGER MCPHERSON |
| 561-805-6716 |
| [email protected] |
| CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| AMENDMENT |
| |
| CORRECTIONS NEEDED - |
| |
| 1) DRAWING A-2 PLEASE SHOW THE SOFFIT FRAMING |
| ATTACHMENT TO THE EXISTING STRUCTURE - ATTACHMENT TYPE, |
| SIZE AND OC SPACING FBC WPB 107.2 |
| |
| 2) WALLS SEPARATING STAGE FROM BACK ROOMS - STORAGE AND |
| DRESSING ROOMS - SHOULD BE FIRE RATED PER FBC 410.5.1 |
| SEPARATION FROM STAGE. |
| THE STAGE SHALL BE SEPARATED FROM DRESSING ROOMS, SCENE |
| DOCKS, PROPERTY ROOMS, WORKSHOPS, STOREROOMS AND |
| COMPARTMENTS APPURTENANT TO THE STAGE AND OTHER PARTS |
| OF THE BUILDING BY FIRE BARRIERS CONSTRUCTED IN |
| ACCORDANCE WITH SECTION 707 OR HORIZONTAL ASSEMBLIES |
| CONSTRUCTED IN ACCORDANCE WITH SECTION 711, OR BOTH. |
| THE FIRE-RESISTANCE RATING SHALL BE NOT LESS THAN 2 |
| HOURS FOR STAGE HEIGHTS GREATER THAN 50 FEET (15 240 |
| MM) AND NOT LESS THAN 1 HOUR FOR STAGE HEIGHTS OF 50 |
| FEET (15 240 MM) OR LESS. |
| |
| 3) WALLS SEPARATING STORAGE FROM DRESSING ROOM SHOULD |
| BE FIRE RATED PER FBC 410.5.2 SEPARATION FROM EACH |
| OTHER. |
| DRESSING ROOMS, SCENE DOCKS, PROPERTY ROOMS, WORKSHOPS, |
| STOREROOMS AND COMPARTMENTS APPURTENANT TO THE STAGE |
| SHALL BE SEPARATED FROM EACH OTHER BY NOT LESS THAN |
| 1-HOUR FIRE BARRIERS CONSTRUCTED IN ACCORDANCE WITH |
| SECTION 707 OR HORIZONTAL ASSEMBLIES CONSTRUCTED IN |
| ACCORDANCE WITH SECTION 711, OR BOTH. |