Plan Review Notes For Permit 22051284 |
Permit Number |
22051284 |
|
Review Stop |
B |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2023-01-24 13:49:37 | BUILDING REVIEW APPROVED WITH PROVISO (NOTE: PROVIDE | | INFORMATION FOR REVIEW PRIOR TO INSTALLATION/INSPECTION | | TO AVOID CONFLICTS/DELAYS): | | 1-PROVIDE PRODUCT APPROVAL FOR: (A)ROOF TILE HIP & | | RIDGE METAL SUPPORT. (B)STRUCTURAL MULLIONS THAT MEETS | | DESIGN PRESSURES FOR WINDOW "J", (C)EXTERIOR OUTSWING | | DOOR ON NEW UNDER STAIR STORAGE. (D)EXTERIOR SOLID | | OUTSWING DOOR ON NEW PRIVACY WALL NEXT TO THE NEW | | STAIRWAY. (E)ENTRY DOOR WITH SIDELITES AS SHOWN ON | | PLANS. (F)FIXED WINDOW SIZE SPECIFIED FOR WINDOW "L" | | (6'-0" X 5'-10"). | | 2-DESIGNER OF RECORD TO APPROVE IN WRITING ALL PRODUCT | | APPROVALS. | | 3-REVISE ENERGY CALCULATIONS: (A)REVISE ITEM #1 ON PAGE | | ONE. THIS IS EXISTING AND NEW CONSTRUCTION (ADDITION). | | (B)REVISE DOORS INFORMATION. THERE ARE NOT WOOD DOORS | | ON THE NORTH AND SOUTH SIDE. (C)REVISE WINDOWS | | INFORMATION TO MATCH PLANS. CHECK WINDOWS AREAS, NUMBER | | OF WINDOWS/GLASS DOORS SHOWN ON PLANS, WINDOW | | ORIENTATION AND WINDOWS OVERHANG DEPTH AND SEPARATION | | AND REVISE AS REQUIRED. | | |
|