2022-12-12 17:30:32 | RESIDENTIAL (R3) ADDITION/ALTERATION SECOND BUILDING |
| REVIEW COMMENTS |
| CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| PERMIT #22051284 |
| 201 SUMMA ST |
| |
| NOTE: |
| BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO |
| MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER |
| THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID |
| CONFLICTS/DELAYS. REVISION FEES APPLY. |
| |
| ***IMPORTANT****CONTRACTOR TO ADVICE IF PROVISO OPTION |
| IS PREFERRED AT THIS TIME OR IF RE-SUBMITTING REQUIRED |
| INFORMATION BEFORE PERMIT ISSUANCE. |
| |
| ***IMPORTANT*** |
| ENERGY CALCULATIONS NEED TO BE CERTIFIED AT THE BOTTOM |
| OF FORM BY THE OWNER OR AUTHORIZED AGENT BEFORE ISSUING |
| THE PERMIT |
| |
| |
| 1-OK. |
| 2-OK. |
| 3-OK. |
| |
| ORIGINAL COMMENT |
| 4- SPECIFY ATTIC ACCESS SIZE AND LOCATION SHOWING |
| COMPLIANCE WITH SEC. R807 FBC-RESIDENTIAL. |
| NOTE: MAKE SURE THERE IS ENOUGH HEADROOM ABOVE ATTIC |
| ACCESS PANEL. |
| |
| RESPONSE: |
| ROOF FRAMING PLAN NEEDS TO BE REVISED TO ALLOW FOR THE |
| ATTIC ACCESS PROPOSED LOCATION AND SIZE. ALSO, IT LOOKS |
| LIKE THE PROPOSED LOCATION MAY NOT PROVIDE THE REQUIRED |
| HEADROOM CLEARANCE. PROVIDE DETAIL SHOWING THE ACTUAL |
| HEADROOM ON THE PROPOSED LOCATION. |
| |
| 5- ENLARGED STAIR PLAN DETAIL 2 ON SHEET A-501: |
| ORIGINAL COMMENT: |
| B)PROVIDE STAIR NOSING DETAIL SHOWING COMPLIANCE WITH |
| SEC. R311.7.5.3 FBC-RESIDENTIAL. |
| |
| RESPONSE: |
| TREAD DIMENSION SHOWN ON DETAIL 10 DOESN'T MATCH TREAD |
| DIMENSION SHOWN ON DETAIL 2. REVISE AS REQUIRED TO |
| MATCH. SEC. 107.2.1 CITY AMENDMENTS. |
| |
| ORIGINAL COMMENT: |
| 6- ENGINEER OF RECORD TO REVISE ROOF SHEATHING NAILING |
| SPECIFICATIONS TO COMPLY WITH NEW 2020 FBC-RESIDENTIAL |
| SPECIFICATIONS. REVISED NAIL SPACING SPECIFIED IN ALL |
| DETAILS AND SPECIFICATIONS SUBMITTED TO COMPLY TABLE |
| R803.2.3.1 FBC-RESIDENTIAL. NAIL SPACING TO BE 4" O.C. |
| NOTE: REVISE SPECIFICATIONS OR PROVIDE CALCULATIONS |
| SHOWING THAT SPECIFIED NAIL TYPE AND SPACING MATCHES OR |
| EXCEEDS TABLE R803.2.3.1 FBC-RESIDENTIAL MINIMUM |
| REQUIREMENTS. |
| |
| RESPONSE: |
| ROOF NOTE #1 ON SHEET S-2 WAS NOT REVISED. |
| |
| 7- OK. |
| |
| 8- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC |
| 61G20-3.001 FOR: |
| (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED |
| SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW |
| PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL |
| PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY |
| DESIGNER OF RECORD PRIOR TO SUBMITTAL): |
| |
| A)OK. |
| |
| ORIGINAL COMMENT: |
| B)ROOF TILE ADHESIVE. TILE BOND NOA 16-0222.01 |
| SUBMITTED EXPIRED ON 08/23/21. NEED CURRENT PRODUCT |
| APPROVAL. ALSO, COORDINATE WITH ROOF TILE COMMENT |
| ABOVE. |
| |
| RESPONSE: |
| REPEAT COMMENT. SAME NOA WAS SUBMITTED. |
| |
| ORIGINAL COMMENT: |
| C)ROOF TILE HIP & RIDGE METAL SUPPORT TO BE USED AS |
| SPECIFIED ON PLANS. |
| |
| RESPONSE: |
| REPEAT COMMENT. NOT ADDRESSED. |
| |
| D)OK. |
| |
| ORIGINAL COMMENT: |
| E)STRUCTURAL MULLIONS AS SHOWN ON PLANS. AND REQUIRED: |
| CLEARLY SPECIFY MULLION SIZE TO BE USED TO VERIFY |
| COMPLIANCE WITH THE CALCULATED DESIGN PRESSURES. |
| NOTE: NEED TO PROVIDE COMPLETE PRODUCT APPROVAL, |
| INCLUDING THE FLORIDA PRODUCT APPROVAL COVER PAGE |
| CORRESPONDING TO DRAWINGS SUBMITTED. |
| |
| RESPONSE: |
| CLEARLY SPECIFY OR MARK MULLION SIZE ON NOA 20-0406.03 |
| SUBMITTED. |
| |
| ORIGINAL COMMENT: |
| F)NEW OUTSIDE OUTSWING DOOR IN EXISTING LIVING ROOM |
| AREA. |
| NOTE: NEED TO PROVIDE COMPLETE PRODUCT APPROVAL, |
| INCLUDING THE FLORIDA PRODUCT APPROVAL COVER PAGE |
| CORRESPONDING TO DRAWINGS SUBMITTED. |
| |
| RESPONSE: |
| PROVIDE COMPLETE PRODUCT APPROVAL INCLUDING THE FLORIDA |
| PRODUCT APPROVAL COVER PAGE THAT CORRESPONDS TO |
| DRAWINGS SUBMITTED. |
| NOTE: THERE ARE SEVERAL DOOR PRODUCT APPROVALS |
| SUBMITTED. CLEARLY LABEL EACH PRODUCT APPROVAL LIKE |
| ENTRY DOOR, STORAGE, LIVING ROOM, ETC TO AVOID |
| CONFLICTS/DELAYS. PLEASE COORDINATE WITH THE PERMIT |
| LIBRARIAN TO SEE WHICH PRODUCT APPROVALS YOU WANT TO BE |
| DELETED. |
| |
| ORIGINAL COMMENT: |
| G)EXTERIOR OUTSWING DOOR ON NEW UNDER STAIR STORAGE. |
| NOTE: NEED TO PROVIDE COMPLETE PRODUCT APPROVAL, |
| INCLUDING THE FLORIDA PRODUCT APPROVAL COVER PAGE |
| CORRESPONDING TO DRAWINGS SUBMITTED. |
| |
| RESPONSE: |
| COORDINATE WITH ITEM ABOVE. |
| |
| ORIGINAL COMMENT: |
| H)EXTERIOR SOLID OUTSWING DOOR ON NEW PRIVACY WALL NEXT |
| TO THE NEW STAIRWAY. |
| |
| RESPONSE: |
| COORDINATE WITH ITEM ABOVE. |
| |
| ORIGINAL COMMENT: |
| 9- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| |
| RESPONSE: |
| COORDINATE WITH ITEM ABOVE. |
| |
| 10- ENERGY CALCULATIONS SUBMITTED: |
| ORIGINAL COMMENT: |
| A) THE ENERGY FORM R405-2020 IS REQUIRED TO BE SIGNED |
| AND DATED BY THE OWNER, ARCHITECT OR OWNER'S LEGALLY |
| DESIGNATED AGENT AT THE BOTTOM OF FORM SUBMITTED AS |
| REQUIRED BY SECTION 553.907, FLORIDA STATUTES, PRIOR TO |
| RECEIVING THE PERMIT TO BEGIN CONSTRUCTION OR |
| RENOVATION. SECTION R101.5.1.1.2 FBC-RESIDENTIAL. |
| |
| RESPONSE: |
| THE BUILDING'S OWNER, THE OWNER'S ARCHITECT, OR OTHER |
| AUTHORIZED AGENT LEGALLY DESIGNATED BY THE OWNER SHALL |
| CERTIFY AT THE OWNER/AGENT LINE AT THE BOTTOM OF FORM |
| THAT THE BUILDING IS IN COMPLIANCE WITH THE CODE, AS |
| PER SECTION 553.907, FLORIDA STATUTES, PRIOR TO |
| RECEIVING THE PERMIT TO BEGIN CONSTRUCTION OR |
| RENOVATION AS REQUIRED BY SECTION R103.1.1.2 FBC-ENERGY |
| CONSERVATION. |
| |
| B)OK. |
| C)OK. |
| |
| ORIGINAL COMMENT: |
| D)IT IS NOT CLEAR IF THE CALCULATIONS ARE DONE FOR THE |
| ENTIRE HOUSE OR JUST THE ADDITION. CALCULATIONS CAN BE |
| DONE EITHER WAY, BUT THEY NEED TO BE CONSISTENT. SEC. |
| R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| |
| RESPONSE: |
| STILL NOT CLEAR. CONDITIONED FLOOR AREA ON ITEM 6 OF |
| PAGE ONE DOESN'T MATCH A/C AREAS SHOWN ON PLANS. SHEET |
| G-001. |
| |
| ORIGINAL COMMENT: |
| E)REVISE/CLARIFY ITEM #1 ON PAGE ONE. EXISTING OR NEW |
| CONSTRUCTION (ADDITION). COORDINATE WITH COMMENT (D) |
| ABOVE. |
| SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| |
| RESPONSE: |
| STILL NO CLEAR. COORDINATE WITH COMMENT (D)ABOVE TO |
| AVOID MORE CONFLICTS/DELAYS. |
| |
| ORIGINAL COMMENT: |
| F)REVISE/CLARIFY ITEM #4 ON PAGE ONE. PROVIDE CORRECT |
| NUMBER OF BEDROOMS. COORDINATE WITH COMMENT (D)ABOVE. |
| SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| |
| RESPONSE: |
| STILL NO CLEAR. COORDINATE WITH COMMENT (D)ABOVE TO |
| AVOID MORE CONFLICTS/DELAYS. |
| |
| ORIGINAL COMMENT: |
| G)REVISE/CLARIFY ITEM #6 ON PAGE ONE. PROVIDE CORRECT |
| CONDITIONED FLOOR AREA. SEE PLANS AND COORDINATE WITH |
| COMMENT (D) ABOVE. |
| SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| |
| RESPONSE: |
| STILL NO CLEAR. COORDINATE WITH COMMENT (D)ABOVE TO |
| AVOID MORE CONFLICTS/DELAYS. |
| |
| ORIGINAL COMMENT: |
| H)REVISE/CLARIFY ITEM #11 ON PAGE ONE. PLANS SHOW |
| UNVENTED ATTIC AND THEY SHOW DIFFERENT R-VALUES FOR |
| CEILING INSULATION DEPENDING ON THE ROOF TYPE. SEE |
| PLANS AND REVISE AS REQUIRED. AND COORDINATE WITH |
| COMMENT (D) ABOVE. |
| SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| |
| RESPONSE: |
| CEILING INSULATION DOESN'T MATCH PLANS. SEE SHEETS |
| A-400 AND A-401 AND REVISE AS REQUIRED. |
| |
| I)OK. |
| |
| ORIGINAL COMMENT: |
| J)REVISE/CLARIFY PROJECT INFORMATION ON PAGE 2. TWO |
| STORY ONLY APPLIES IF ENTIRE HOUSE IS CONSIDERED. |
| ADDITION ALONE IS ONE STORY. SEE PLANS AND COORDINATE |
| WITH COMMENT (D) ABOVE. |
| SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| |
| RESPONSE: |
| STILL NO CLEAR. COORDINATE WITH COMMENT (D)ABOVE TO |
| AVOID MORE CONFLICTS/DELAYS. |
| |
| ORIGINAL COMMENT: |
| K)REVISE/CLARIFY SPACES INFORMATION ON PAGE 2. KITCHEN |
| ONLY APPLIES TO ENTIRE HOUSE. SEE PLANS AND REVISE AS |
| REQUIRED. AND COORDINATE WITH COMMENT (D) ABOVE. |
| SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| |
| RESPONSE: |
| STILL NO CLEAR. COORDINATE WITH COMMENT (D)ABOVE TO |
| AVOID MORE CONFLICTS/DELAYS. |
| |
| ORIGINAL COMMENT: |
| L)REVISE/CLARIFY ROOF TYPE INFORMATION ON PAGE 2. IT |
| LOOKS LIKE THERE ARE MORE GABLES IN THIS HOUSE. AND IS |
| MISSING THE ROOF AREA. SEE PLANS AND REVISE AS |
| REQUIRED. AND COORDINATE WITH COMMENT (D) ABOVE. |
| SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| |
| RESPONSE: |
| STILL NO CLEAR. COORDINATE WITH COMMENT (D)ABOVE TO |
| AVOID MORE CONFLICTS/DELAYS. |
| NOTE: THERE ARE GABLE ROOFS IN THIS HOUSE ALSO. PROVIDE |
| REQUIRED INFORMATION. |
| |
| M)OK. |
| |
| ORIGINAL COMMENT: |
| N)REVISE/CLARIFY DOORS INFORMATION ON PAGE 3. WHERE ARE |
| THE WOOD DOORS ON THE NORTH AND SOUTH SIDE? SEE PLANS |
| AND REVISE AS REQUIRED. AND COORDINATE WITH COMMENT (D) |
| ABOVE. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| |
| RESPONSE: |
| STILL NO CLEAR. COORDINATE WITH COMMENT (D)ABOVE TO |
| AVOID MORE CONFLICTS/DELAYS. |
| NOTE: PLANS DON'T SHOW WOOD DOORS. |
| |
| ORIGINAL COMMENT: |
| O)REVISE/CLARIFY WINDOWS INFORMATION ON PAGE 3. REVISE |
| WINDOWS AREA, AND OVERHANG DEPTH AND SEPARATION TO |
| MATCH PLANS. SEE PLANS AND REVISE AS REQUIRED. AND |
| COORDINATE WITH COMMENT (D) ABOVE. SEC. R101.5.1.1.2 |
| FBC-ENERGY CONSERVATION. |
| |
| RESPONSE: |
| STILL NO CLEAR. COORDINATE WITH COMMENT (D)ABOVE TO |
| AVOID MORE CONFLICTS/DELAYS. |
| NOTE: WINDOWS OVERHANG DEPTH AND SEPARATION DON'T MATCH |
| PLANS. SEE ELEVATIONS. |
| |
| ORIGINAL COMMENT: |
| P)REVISE/CLARIFY GARAGE INFORMATION ON PAGE 3. |
| COORDINATE WITH COMMENT (D) ABOVE. SEC. R101.5.1.1.2 |
| FBC-ENERGY CONSERVATION. |
| |
| RESPONSE: |
| STILL NO CLEAR. COORDINATE WITH COMMENT (D)ABOVE TO |
| AVOID MORE CONFLICTS/DELAYS. |
| |
| ORIGINAL COMMENT: |
| Q)BUILDER TO SIGN AND COMPLETE THE ENERGY PERFORMANCE |
| LEVEL (EPL) DISPLAY CARD. SEC. R405.4.3 FBC- ENERGY |
| CONSERVATION. |
| |
| RESPONSE: |
| NO ADDRESSED. |
| |
| WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND |
| HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE |
| REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| QUESTIONS REGARDING THESE COMMENTS, |
| JULIO GOMEZ |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| DEVELOPMENT SERVICES DEPARTMENT |
| BUILDING DIVISION |
| (561)805-6712 |
| [email protected] |
| |
| |