2022-07-26 15:40:06RESIDENTIAL (R3) ADDITION/ALTERATION BUILDING REVIEW
 COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #22051284 201 SUMMA ST
  
 NOTE:
 ADDITIONS SEC. 606 FBC-EXISTING BUILDING. SEC. 1101.1
 FBC-EXISTING BUILDING. ALL NEW CONSTRUCTION ELEMENTS,
 COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE
 REQUIREMENTS OF THE FLORIDA BUILDING CODE.
  
 NOTE:
 LEVEL 3 ALTERATION. SEC. 604 FBC-EXISTING BUILDING.
 SEC. 901.2 FBC-EXISTING BUILDING. SEC. 801.3
 FBC-EXISTING BUILDING. ALL NEW CONSTRUCTION ELEMENTS,
 COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE
 REQUIREMENTS OF THE FLORIDA BUILDING CODE.
  
 1- PROPOSED WORK AFFECTS THE LOT DRAINAGE. PROVIDE
 DRAINAGE PLAN SHOWING HOW THE SURFACE DRAINAGE IS KEPT
 WITHIN THE LOT AND NOT DIVERTED TO ADJACENT PROPERTIES.
 PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE
 FOLLOWING SECTIONS: R401.3 FBC-RESIDENTIAL. SEC.
 107.2.5 CITY AMENDMENTS AND SEC. 110.9 CITY AMENDMENTS.
 NOTE: DRAINAGE PLAN TO SHOW THE EXISTING AND PROPOSED
 GRADE ELEVATIONS SHOWING HOW KEEPING WATER AWAY FROM
 ADJACENT PROPERTIES.
  
 2- SIZE OF NEW ENTRY DOOR IS NOT GIVEN. SPECIFY DOOR
 SIZE TO VERIFY COMPLIANCE WITH EGRESS SEC. R11.2
 FBC-RESIDENTIAL.
 NOTE: DOOR SCHEDULE ON SHEET G-004 IS NOT SHOWING ANY
 OF THE EXTERIOR DOORS. ENTRY DOOR, DOOR E100 BY THE
 EXISTING LIVING ROOM, DOOR E103 ON NEW STORAGE ROOM
 UNDERNEATH NEW EXTERIOR STAIRS AND SOLID DOOR E102 ON
 PRIVACY WALL. PROVIDE THIS INFORMATION.
  
 3- BEDROOM #1 AND BEDROOM #2 CASEMENT EGRESS WINDOWS.
 TYPICALLY, 30 INCH WIDE CASEMENT WINDOWS DON'T PROVIDE
 THE REQUIRED CLEAR WIDTH OPENING BECAUSE OF THE
 OPERATING HINGE. PRODUCT APPROVAL SUBMITTED IS FOR PGT
 WINDOWS. PGT WINDOWS HAVE A SPECIAL "EGRESS HINGE".
 DESIGNER OF RECORD TO SPECIFY ON PLANS THE EGRESS HINGE
 ON THE PGT WINDOWS OR SPECIFY OTHER WINDOW SIZE THAT
 MEETS THE BEDROOM EGRESS REQUIREMENTS WITHOUT THE
 SPECIAL REQUEST. SEC. 107.2.1 CITY AMENDMENTS. SEC.
 R310.2.1 FBC-RESIDENTIAL.
 NOTE: REVISE/CLARIFY COMMENTS ON WINDOW SCHEDULE.
 WINDOW MARKED "D" IS THE EGRESS WINDOW NOT "A". ALSO,
 WINDOW "J" COMMENTS CALL FOR 2 PANEL. THESE DOESN'T
 MATCH PLANS AND ELEVATIONS.
  
 4- SPECIFY ATTIC ACCESS SIZE AND LOCATION SHOWING
 COMPLIANCE WITH SEC. R807 FBC-RESIDENTIAL.
 NOTE: MAKE SURE THERE IS ENOUGH HEADROOM ABOVE ATTIC
 ACCESS PANEL.
  
 5- ENLARGED STAIR PLAN DETAIL 2 ON SHEET A-501:
 A) NEED TO PROVIDE HANDRAIL SHOWING COMPLIANCE WITH
 SEC. R311.7.8 FBC-RESIDENTIAL.
  
 B)PROVIDE STAIR NOSING DETAIL SHOWING COMPLIANCE WITH
 SEC. R311.7.5.3 FBC-RESIDENTIAL.
  
 C)WINDER TREAD AT TOP OF STAIR NEED TO COMPLY WITH SEC.
 R311.7.5.2.1 FBC-RESIDENTIAL. SPECIFY DIMENSIONS.
  
 D)HEIGHT OF THE GUARDRAIL AT THE CORNER OF TOP LANDING
 OF STAIR DOESN'T COMPLY WITH SEC. R312.1
 FBC-RESIDENTIAL. REVISE ALL DRAWINGS AS REQUIRED. SEE
 STAIR SECTION A ON SHEET A-501 AND DETAIL 3 ON SHEET
 A-500.
  
 6- ENGINEER OF RECORD TO REVISE ROOF SHEATHING NAILING
 SPECIFICATIONS TO COMPLY WITH NEW 2020 FBC-RESIDENTIAL
 SPECIFICATIONS. REVISED NAIL SPACING SPECIFIED IN ALL
 DETAILS AND SPECIFICATIONS SUBMITTED TO COMPLY TABLE
 R803.2.3.1 FBC-RESIDENTIAL. NAIL SPACING TO BE 4" O.C.
 NOTE: REVISE SPECIFICATIONS OR PROVIDE CALCULATIONS
 SHOWING THAT SPECIFIED NAIL TYPE AND SPACING MATCHES OR
 EXCEEDS TABLE R803.2.3.1 FBC-RESIDENTIAL MINIMUM
 REQUIREMENTS.
  
 7-ENGINEER OF RECORD TO SPECIFY DESIGN PRESSURES FOR
 SOLID DOOR E102 LOCATED IN THE PRIVACY WALL NEXT TO THE
 NEW STAIRWAY LEADING TO THE TERRACE AREA. SEC.
 107.2.1.2 CITY AMENDMENTS. SEC. R301.2.1
 FBC-RESIDENTIAL.
  
 8- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW
 PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL
 PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY
 DESIGNER OF RECORD PRIOR TO SUBMITTAL):
  
 A)ROOF TILE. NOA 18-0509.17 SUBMITTED EXPIRED ON
 04/26/22. NEED CURRENT PRODUCT APPROVAL.
 ALSO, CLEARLY MARK ADHESIVE PADDY SIZE TO BE USED AS
 REQUIRED BY CITY POLICY FOR ALL ROOFING PERMITS TO
 VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC
 R301.2.1 FBC-RESIDENTIAL.
 NOTE: ROOF TILE ADHESIVE PRODUCT APPROVAL SUBMITTED IS
 FOR TILE BOND. ACCORDING TO ROOF TILE NOA THE MINIMUM
 ATTACHMENT RESISTANCE USING TILE BOND ADHESIVE IS
 31.3FT-LBF. ACCORDING TO FRSA MANUAL THE MINIMUM
 REQUIRED UPLIFT MOMENT FOR TILE AT HIS HOUSE IS MORE
 THAN 31.3FT-LBF. NEED TO SPECIFY OTHER TILE ADHESIVE
 THAT MEETS OR EXCEEDS THE MINIMUM REQUIRED UPLIFT
 MOMENT FOR TILE. OR PROVIDE CALCULATIONS SHOWING
 COMPLIANCE WITH TILE BOND ADHESIVE.
  
 NOTE; THERE ARE TWO DIFFERENT ROOF TILE NOA'S
 SUBMITTED. CLARIFY WHICH ONE IS GOING TO BE USED TO
 AVOID CONFLICTS/DELAYS.
  
 B)ROOF TILE ADHESIVE. TILE BOND NOA 16-0222.01
 SUBMITTED EXPIRED ON 08/23/21. NEED CURRENT PRODUCT
 APPROVAL. ALSO, COORDINATE WITH ROOF TILE COMMENT
 ABOVE.
  
 C)ROOF TILE HIP & RIDGE METAL SUPPORT TO BE USED.
  
 D)TERRACE UNDERLAYMENT THAT IS DESIGNED TO BE INSTALLED
 WITH FINISH FLOOR SPECIFIED ON PLANS. DESIGNER OF
 RECORD TO PROVIDE SPECIFICATIONS FOR FINISH FLOORING.
 NOTE: CLEARLY IDENTIFY SPECIFIC ASSEMBLY TO BE
 INSTALLED AND RAS 117 CALCULATIONS MAY BE REQUIRED IF
 SELECTED ASSEMBLY DOESN'T MEET THE DESIGN PRESSURES FOR
 ALL ZONES.
  
 E)STRUCTURAL MULLIONS AS SHOWN ON PLANS. AND REQUIRED:
 CLEARLY SPECIFY MULLION SIZE TO BE USED TO VERIFY
 COMPLIANCE WITH THE CALCULATED DESIGN PRESSURES.
 NOTE: NEED TO PROVIDE COMPLETE PRODUCT APPROVAL,
 INCLUDING THE FLORIDA PRODUCT APPROVAL COVER PAGE
 CORRESPONDING TO DRAWINGS SUBMITTED.
  
 F)NEW OUTSIDE OUTSWING DOOR IN EXISTING LIVING ROOM
 AREA.
 NOTE: NEED TO PROVIDE COMPLETE PRODUCT APPROVAL,
 INCLUDING THE FLORIDA PRODUCT APPROVAL COVER PAGE
 CORRESPONDING TO DRAWINGS SUBMITTED.
  
 G)EXTERIOR OUTSWING DOOR ON NEW UNDER STAIR STORAGE.
 NOTE: NEED TO PROVIDE COMPLETE PRODUCT APPROVAL,
 INCLUDING THE FLORIDA PRODUCT APPROVAL COVER PAGE
 CORRESPONDING TO DRAWINGS SUBMITTED.
  
 H)EXTERIOR SOLID OUTSWING DOOR ON NEW PRIVACY WALL NEXT
 TO THE NEW STAIRWAY.
  
 9- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 10- ENERGY CALCULATIONS SUBMITTED:
 A) THE ENERGY FORM R405-2020 IS REQUIRED TO BE SIGNED
 AND DATED BY THE OWNER, ARCHITECT OR OWNER'S LEGALLY
 DESIGNATED AGENT AT THE BOTTOM OF FORM SUBMITTED AS
 REQUIRED BY SECTION 553.907, FLORIDA STATUTES, PRIOR TO
 RECEIVING THE PERMIT TO BEGIN CONSTRUCTION OR
 RENOVATION. SECTION R101.5.1.1.2 FBC-RESIDENTIAL.
  
 B)PROVIDE THE NAME (NOT SIGNATURE) OF PERSON PERFORMING
 THE ANALYSIS AND GENERATING THE REPORT AS REQUIRED BY
 SEC. R405.4.2.1 FBC- ENERGY CONSERVATION.
  
 C) PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING OWNER'S NAME, BUILDER'S NAME, PERMIT OFFICE
 AND JURISDICTION NUMBER (THIS JURISDICTION IS 604700).
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 D)IT IS NOT CLEAR IF THE CALCULATIONS ARE DONE FOR THE
 ENTIRE HOUSE OR JUST THE ADDITION. CALCULATIONS CAN BE
 DONE EITHER WAY, BUT THEY NEED TO BE CONSISTENT. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 E)REVISE/CLARIFY ITEM #1 ON PAGE ONE. EXISTING OR NEW
 CONSTRUCTION (ADDITION). COORDINATE WITH COMMENT (D)
 ABOVE.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 F)REVISE/CLARIFY ITEM #4 ON PAGE ONE. PROVIDE CORRECT
 NUMBER OF BEDROOMS. COORDINATE WITH COMMENT (D) ABOVE.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 G)REVISE/CLARIFY ITEM #6 ON PAGE ONE. PROVIDE CORRECT
 CONDITIONED FLOOR AREA. SEE PLANS AND COORDINATE WITH
 COMMENT (D) ABOVE.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 H)REVISE/CLARIFY ITEM #11 ON PAGE ONE. PLANS SHOW
 UNVENTED ATTIC AND THEY SHOW DIFFERENT R-VALUES FOR
 CEILING INSULATION DEPENDING ON THE ROOF TYPE. SEE
 PLANS AND REVISE AS REQUIRED. AND COORDINATE WITH
 COMMENT (D) ABOVE.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 I)REVISE/CLARIFY ITEM #15 ON PAGE ONE. WATER HEATER IS
 GAS NOT ELECTRIC. SEE PLANS AND COORDINATE WITH COMMENT
 (D) ABOVE.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 J)REVISE/CLARIFY PROJECT INFORMATION ON PAGE 2. TWO
 STORY ONLY APPLIES IF ENTIRE HOUSE IS CONSIDERED.
 ADDITION ALONE IS ONE STORY. SEE PLANS AND COORDINATE
 WITH COMMENT (D) ABOVE.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 K)REVISE/CLARIFY SPACES INFORMATION ON PAGE 2. KITCHEN
 ONLY APPLIES TO ENTIRE HOUSE. SEE PLANS AND REVISE AS
 REQUIRED. AND COORDINATE WITH COMMENT (D) ABOVE.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 L)REVISE/CLARIFY ROOF TYPE INFORMATION ON PAGE 2. IT
 LOOKS LIKE THERE ARE MORE GABLES IN THIS HOUSE. AND IS
 MISSING THE ROOF AREA. SEE PLANS AND REVISE AS
 REQUIRED. AND COORDINATE WITH COMMENT (D) ABOVE.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 M)REVISE/CLARIFY ATTIC INFORMATION ON PAGE 2. THERE IS
 NOT 1/300 VENT RATIO. SEE PLANS AND REVISE AS REQUIRED.
 AND COORDINATE WITH COMMENT (D) ABOVE. AND IS MISSING
 THE ROOF AREA. SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION.
  
 N)REVISE/CLARIFY DOORS INFORMATION ON PAGE 3. WHERE ARE
 THE WOOD DOORS ON THE NORTH AND SOUTH SIDE? SEE PLANS
 AND REVISE AS REQUIRED. AND COORDINATE WITH COMMENT (D)
 ABOVE. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 O)REVISE/CLARIFY WINDOWS INFORMATION ON PAGE 3. REVISE
 WINDOWS AREA, AND OVERHANG DEPTH AND SEPARATION TO
 MATCH PLANS. SEE PLANS AND REVISE AS REQUIRED. AND
 COORDINATE WITH COMMENT (D) ABOVE. SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION.
  
 P)REVISE/CLARIFY GARAGE INFORMATION ON PAGE 3.
 COORDINATE WITH COMMENT (D) ABOVE. SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION.
  
 Q)BUILDER TO SIGN AND COMPLETE THE ENERGY PERFORMANCE
 LEVEL (EPL) DISPLAY CARD. SEC. R405.4.3 FBC- ENERGY
 CONSERVATION.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND
 HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE
 REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]