2022-07-26 15:40:06 | RESIDENTIAL (R3) ADDITION/ALTERATION BUILDING REVIEW |
| COMMENTS |
| CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| PERMIT #22051284 201 SUMMA ST |
| |
| NOTE: |
| ADDITIONS SEC. 606 FBC-EXISTING BUILDING. SEC. 1101.1 |
| FBC-EXISTING BUILDING. ALL NEW CONSTRUCTION ELEMENTS, |
| COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE |
| REQUIREMENTS OF THE FLORIDA BUILDING CODE. |
| |
| NOTE: |
| LEVEL 3 ALTERATION. SEC. 604 FBC-EXISTING BUILDING. |
| SEC. 901.2 FBC-EXISTING BUILDING. SEC. 801.3 |
| FBC-EXISTING BUILDING. ALL NEW CONSTRUCTION ELEMENTS, |
| COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE |
| REQUIREMENTS OF THE FLORIDA BUILDING CODE. |
| |
| 1- PROPOSED WORK AFFECTS THE LOT DRAINAGE. PROVIDE |
| DRAINAGE PLAN SHOWING HOW THE SURFACE DRAINAGE IS KEPT |
| WITHIN THE LOT AND NOT DIVERTED TO ADJACENT PROPERTIES. |
| PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE |
| FOLLOWING SECTIONS: R401.3 FBC-RESIDENTIAL. SEC. |
| 107.2.5 CITY AMENDMENTS AND SEC. 110.9 CITY AMENDMENTS. |
| NOTE: DRAINAGE PLAN TO SHOW THE EXISTING AND PROPOSED |
| GRADE ELEVATIONS SHOWING HOW KEEPING WATER AWAY FROM |
| ADJACENT PROPERTIES. |
| |
| 2- SIZE OF NEW ENTRY DOOR IS NOT GIVEN. SPECIFY DOOR |
| SIZE TO VERIFY COMPLIANCE WITH EGRESS SEC. R11.2 |
| FBC-RESIDENTIAL. |
| NOTE: DOOR SCHEDULE ON SHEET G-004 IS NOT SHOWING ANY |
| OF THE EXTERIOR DOORS. ENTRY DOOR, DOOR E100 BY THE |
| EXISTING LIVING ROOM, DOOR E103 ON NEW STORAGE ROOM |
| UNDERNEATH NEW EXTERIOR STAIRS AND SOLID DOOR E102 ON |
| PRIVACY WALL. PROVIDE THIS INFORMATION. |
| |
| 3- BEDROOM #1 AND BEDROOM #2 CASEMENT EGRESS WINDOWS. |
| TYPICALLY, 30 INCH WIDE CASEMENT WINDOWS DON'T PROVIDE |
| THE REQUIRED CLEAR WIDTH OPENING BECAUSE OF THE |
| OPERATING HINGE. PRODUCT APPROVAL SUBMITTED IS FOR PGT |
| WINDOWS. PGT WINDOWS HAVE A SPECIAL "EGRESS HINGE". |
| DESIGNER OF RECORD TO SPECIFY ON PLANS THE EGRESS HINGE |
| ON THE PGT WINDOWS OR SPECIFY OTHER WINDOW SIZE THAT |
| MEETS THE BEDROOM EGRESS REQUIREMENTS WITHOUT THE |
| SPECIAL REQUEST. SEC. 107.2.1 CITY AMENDMENTS. SEC. |
| R310.2.1 FBC-RESIDENTIAL. |
| NOTE: REVISE/CLARIFY COMMENTS ON WINDOW SCHEDULE. |
| WINDOW MARKED "D" IS THE EGRESS WINDOW NOT "A". ALSO, |
| WINDOW "J" COMMENTS CALL FOR 2 PANEL. THESE DOESN'T |
| MATCH PLANS AND ELEVATIONS. |
| |
| 4- SPECIFY ATTIC ACCESS SIZE AND LOCATION SHOWING |
| COMPLIANCE WITH SEC. R807 FBC-RESIDENTIAL. |
| NOTE: MAKE SURE THERE IS ENOUGH HEADROOM ABOVE ATTIC |
| ACCESS PANEL. |
| |
| 5- ENLARGED STAIR PLAN DETAIL 2 ON SHEET A-501: |
| A) NEED TO PROVIDE HANDRAIL SHOWING COMPLIANCE WITH |
| SEC. R311.7.8 FBC-RESIDENTIAL. |
| |
| B)PROVIDE STAIR NOSING DETAIL SHOWING COMPLIANCE WITH |
| SEC. R311.7.5.3 FBC-RESIDENTIAL. |
| |
| C)WINDER TREAD AT TOP OF STAIR NEED TO COMPLY WITH SEC. |
| R311.7.5.2.1 FBC-RESIDENTIAL. SPECIFY DIMENSIONS. |
| |
| D)HEIGHT OF THE GUARDRAIL AT THE CORNER OF TOP LANDING |
| OF STAIR DOESN'T COMPLY WITH SEC. R312.1 |
| FBC-RESIDENTIAL. REVISE ALL DRAWINGS AS REQUIRED. SEE |
| STAIR SECTION A ON SHEET A-501 AND DETAIL 3 ON SHEET |
| A-500. |
| |
| 6- ENGINEER OF RECORD TO REVISE ROOF SHEATHING NAILING |
| SPECIFICATIONS TO COMPLY WITH NEW 2020 FBC-RESIDENTIAL |
| SPECIFICATIONS. REVISED NAIL SPACING SPECIFIED IN ALL |
| DETAILS AND SPECIFICATIONS SUBMITTED TO COMPLY TABLE |
| R803.2.3.1 FBC-RESIDENTIAL. NAIL SPACING TO BE 4" O.C. |
| NOTE: REVISE SPECIFICATIONS OR PROVIDE CALCULATIONS |
| SHOWING THAT SPECIFIED NAIL TYPE AND SPACING MATCHES OR |
| EXCEEDS TABLE R803.2.3.1 FBC-RESIDENTIAL MINIMUM |
| REQUIREMENTS. |
| |
| 7-ENGINEER OF RECORD TO SPECIFY DESIGN PRESSURES FOR |
| SOLID DOOR E102 LOCATED IN THE PRIVACY WALL NEXT TO THE |
| NEW STAIRWAY LEADING TO THE TERRACE AREA. SEC. |
| 107.2.1.2 CITY AMENDMENTS. SEC. R301.2.1 |
| FBC-RESIDENTIAL. |
| |
| 8- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC |
| 61G20-3.001 FOR: |
| (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED |
| SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW |
| PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL |
| PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY |
| DESIGNER OF RECORD PRIOR TO SUBMITTAL): |
| |
| A)ROOF TILE. NOA 18-0509.17 SUBMITTED EXPIRED ON |
| 04/26/22. NEED CURRENT PRODUCT APPROVAL. |
| ALSO, CLEARLY MARK ADHESIVE PADDY SIZE TO BE USED AS |
| REQUIRED BY CITY POLICY FOR ALL ROOFING PERMITS TO |
| VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC |
| R301.2.1 FBC-RESIDENTIAL. |
| NOTE: ROOF TILE ADHESIVE PRODUCT APPROVAL SUBMITTED IS |
| FOR TILE BOND. ACCORDING TO ROOF TILE NOA THE MINIMUM |
| ATTACHMENT RESISTANCE USING TILE BOND ADHESIVE IS |
| 31.3FT-LBF. ACCORDING TO FRSA MANUAL THE MINIMUM |
| REQUIRED UPLIFT MOMENT FOR TILE AT HIS HOUSE IS MORE |
| THAN 31.3FT-LBF. NEED TO SPECIFY OTHER TILE ADHESIVE |
| THAT MEETS OR EXCEEDS THE MINIMUM REQUIRED UPLIFT |
| MOMENT FOR TILE. OR PROVIDE CALCULATIONS SHOWING |
| COMPLIANCE WITH TILE BOND ADHESIVE. |
| |
| NOTE; THERE ARE TWO DIFFERENT ROOF TILE NOA'S |
| SUBMITTED. CLARIFY WHICH ONE IS GOING TO BE USED TO |
| AVOID CONFLICTS/DELAYS. |
| |
| B)ROOF TILE ADHESIVE. TILE BOND NOA 16-0222.01 |
| SUBMITTED EXPIRED ON 08/23/21. NEED CURRENT PRODUCT |
| APPROVAL. ALSO, COORDINATE WITH ROOF TILE COMMENT |
| ABOVE. |
| |
| C)ROOF TILE HIP & RIDGE METAL SUPPORT TO BE USED. |
| |
| D)TERRACE UNDERLAYMENT THAT IS DESIGNED TO BE INSTALLED |
| WITH FINISH FLOOR SPECIFIED ON PLANS. DESIGNER OF |
| RECORD TO PROVIDE SPECIFICATIONS FOR FINISH FLOORING. |
| NOTE: CLEARLY IDENTIFY SPECIFIC ASSEMBLY TO BE |
| INSTALLED AND RAS 117 CALCULATIONS MAY BE REQUIRED IF |
| SELECTED ASSEMBLY DOESN'T MEET THE DESIGN PRESSURES FOR |
| ALL ZONES. |
| |
| E)STRUCTURAL MULLIONS AS SHOWN ON PLANS. AND REQUIRED: |
| CLEARLY SPECIFY MULLION SIZE TO BE USED TO VERIFY |
| COMPLIANCE WITH THE CALCULATED DESIGN PRESSURES. |
| NOTE: NEED TO PROVIDE COMPLETE PRODUCT APPROVAL, |
| INCLUDING THE FLORIDA PRODUCT APPROVAL COVER PAGE |
| CORRESPONDING TO DRAWINGS SUBMITTED. |
| |
| F)NEW OUTSIDE OUTSWING DOOR IN EXISTING LIVING ROOM |
| AREA. |
| NOTE: NEED TO PROVIDE COMPLETE PRODUCT APPROVAL, |
| INCLUDING THE FLORIDA PRODUCT APPROVAL COVER PAGE |
| CORRESPONDING TO DRAWINGS SUBMITTED. |
| |
| G)EXTERIOR OUTSWING DOOR ON NEW UNDER STAIR STORAGE. |
| NOTE: NEED TO PROVIDE COMPLETE PRODUCT APPROVAL, |
| INCLUDING THE FLORIDA PRODUCT APPROVAL COVER PAGE |
| CORRESPONDING TO DRAWINGS SUBMITTED. |
| |
| H)EXTERIOR SOLID OUTSWING DOOR ON NEW PRIVACY WALL NEXT |
| TO THE NEW STAIRWAY. |
| |
| 9- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| |
| 10- ENERGY CALCULATIONS SUBMITTED: |
| A) THE ENERGY FORM R405-2020 IS REQUIRED TO BE SIGNED |
| AND DATED BY THE OWNER, ARCHITECT OR OWNER'S LEGALLY |
| DESIGNATED AGENT AT THE BOTTOM OF FORM SUBMITTED AS |
| REQUIRED BY SECTION 553.907, FLORIDA STATUTES, PRIOR TO |
| RECEIVING THE PERMIT TO BEGIN CONSTRUCTION OR |
| RENOVATION. SECTION R101.5.1.1.2 FBC-RESIDENTIAL. |
| |
| B)PROVIDE THE NAME (NOT SIGNATURE) OF PERSON PERFORMING |
| THE ANALYSIS AND GENERATING THE REPORT AS REQUIRED BY |
| SEC. R405.4.2.1 FBC- ENERGY CONSERVATION. |
| |
| C) PROVIDE COMPLETE INFORMATION ON TOP OF FORM, |
| INCLUDING OWNER'S NAME, BUILDER'S NAME, PERMIT OFFICE |
| AND JURISDICTION NUMBER (THIS JURISDICTION IS 604700). |
| SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| |
| D)IT IS NOT CLEAR IF THE CALCULATIONS ARE DONE FOR THE |
| ENTIRE HOUSE OR JUST THE ADDITION. CALCULATIONS CAN BE |
| DONE EITHER WAY, BUT THEY NEED TO BE CONSISTENT. SEC. |
| R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| |
| E)REVISE/CLARIFY ITEM #1 ON PAGE ONE. EXISTING OR NEW |
| CONSTRUCTION (ADDITION). COORDINATE WITH COMMENT (D) |
| ABOVE. |
| SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| |
| F)REVISE/CLARIFY ITEM #4 ON PAGE ONE. PROVIDE CORRECT |
| NUMBER OF BEDROOMS. COORDINATE WITH COMMENT (D) ABOVE. |
| SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| |
| G)REVISE/CLARIFY ITEM #6 ON PAGE ONE. PROVIDE CORRECT |
| CONDITIONED FLOOR AREA. SEE PLANS AND COORDINATE WITH |
| COMMENT (D) ABOVE. |
| SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| |
| H)REVISE/CLARIFY ITEM #11 ON PAGE ONE. PLANS SHOW |
| UNVENTED ATTIC AND THEY SHOW DIFFERENT R-VALUES FOR |
| CEILING INSULATION DEPENDING ON THE ROOF TYPE. SEE |
| PLANS AND REVISE AS REQUIRED. AND COORDINATE WITH |
| COMMENT (D) ABOVE. |
| SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| |
| I)REVISE/CLARIFY ITEM #15 ON PAGE ONE. WATER HEATER IS |
| GAS NOT ELECTRIC. SEE PLANS AND COORDINATE WITH COMMENT |
| (D) ABOVE. |
| SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| |
| J)REVISE/CLARIFY PROJECT INFORMATION ON PAGE 2. TWO |
| STORY ONLY APPLIES IF ENTIRE HOUSE IS CONSIDERED. |
| ADDITION ALONE IS ONE STORY. SEE PLANS AND COORDINATE |
| WITH COMMENT (D) ABOVE. |
| SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| |
| K)REVISE/CLARIFY SPACES INFORMATION ON PAGE 2. KITCHEN |
| ONLY APPLIES TO ENTIRE HOUSE. SEE PLANS AND REVISE AS |
| REQUIRED. AND COORDINATE WITH COMMENT (D) ABOVE. |
| SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| |
| L)REVISE/CLARIFY ROOF TYPE INFORMATION ON PAGE 2. IT |
| LOOKS LIKE THERE ARE MORE GABLES IN THIS HOUSE. AND IS |
| MISSING THE ROOF AREA. SEE PLANS AND REVISE AS |
| REQUIRED. AND COORDINATE WITH COMMENT (D) ABOVE. |
| SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| |
| M)REVISE/CLARIFY ATTIC INFORMATION ON PAGE 2. THERE IS |
| NOT 1/300 VENT RATIO. SEE PLANS AND REVISE AS REQUIRED. |
| AND COORDINATE WITH COMMENT (D) ABOVE. AND IS MISSING |
| THE ROOF AREA. SEC. R101.5.1.1.2 FBC-ENERGY |
| CONSERVATION. |
| |
| N)REVISE/CLARIFY DOORS INFORMATION ON PAGE 3. WHERE ARE |
| THE WOOD DOORS ON THE NORTH AND SOUTH SIDE? SEE PLANS |
| AND REVISE AS REQUIRED. AND COORDINATE WITH COMMENT (D) |
| ABOVE. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| |
| O)REVISE/CLARIFY WINDOWS INFORMATION ON PAGE 3. REVISE |
| WINDOWS AREA, AND OVERHANG DEPTH AND SEPARATION TO |
| MATCH PLANS. SEE PLANS AND REVISE AS REQUIRED. AND |
| COORDINATE WITH COMMENT (D) ABOVE. SEC. R101.5.1.1.2 |
| FBC-ENERGY CONSERVATION. |
| |
| P)REVISE/CLARIFY GARAGE INFORMATION ON PAGE 3. |
| COORDINATE WITH COMMENT (D) ABOVE. SEC. R101.5.1.1.2 |
| FBC-ENERGY CONSERVATION. |
| |
| Q)BUILDER TO SIGN AND COMPLETE THE ENERGY PERFORMANCE |
| LEVEL (EPL) DISPLAY CARD. SEC. R405.4.3 FBC- ENERGY |
| CONSERVATION. |
| |
| WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND |
| HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE |
| REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| QUESTIONS REGARDING THESE COMMENTS, |
| JULIO GOMEZ |