2022-06-10 16:25:53 | 1ST REVIEW FBC-2020 PLUMBING/MECHANICAL REVIEW |
| PERMIT- 22051282 |
| 6/10/2022 |
| |
| CODES IN EFFECT: |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 |
| FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) THE WATER METERS, VALVES, AND OTHER COMPONENT |
| SUBMITTALS SHALL BE REVIEWED AND APPROVED BY THE |
| BUILDING ENGINEER OR ARCHITECT OF RECORD- SEC. 107.3.4 |
| WPB. PLEASE RESUBMIT STAMPED COPIES. |
| |
| 2) SHEETS P-01- P-09: INDICATE THE MAKES AND MODEL |
| NUMBERS OF THE METERS AND VALVES ON THE PLAN- SEC. |
| 107.2.1 WPB. |
| |
| 3) P-01- P-09: CLARIFY IF THE NEW METERS AND VALVES ARE |
| BEING INSTALLED IN PLENUM SPACES, AND VERIFY THE METER |
| ASSEMBLIES ARE PLENUM RATED- SEC. 602.2.1- 602.2.1.8 |
| FBC M. |
| |
| 4) SUBMIT MANUFACTURER?S SPECIFICATIONS INDICATING THE |
| VALVES CONFORM TO ONE OF THE STANDARDS LISTED IN TABLE |
| 605.7 FBC P. |
| |
| 5) THE SUBMITTED PLANS SHALL BEAR THE PRINTED NAME, |
| SIGNATURE, AND THE LICENSE NUMBER OF THE CONTRACTOR OR |
| QUALIFIER WHO PREPARED THE DRAWINGS- SEC. 107.1 AND FL. |
| STATUTES 471.003(2)(H) & 471.025. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |