2022-06-09 07:37:50ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. NOT ENOUGH INFORMATION SHOWN. WHERE IS OVERCURRENT
 PROTECTION FOR 200 AND 125AMP INTERIOR PANELS. FEED
 THROUGH LUGS FOR 200AMP? 2 POLE 125AMP BREAKER FOR THE
 125AMP IN METER MAIN COMBO? MUST SHOW ALL PERTINENT
 INFORMATION ON PLAN. FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.