2022-06-10 16:42:48PROVIDE A COMPLETE OUTDOOR AIR CALCULATION FOR EACH USE
 OF SPACE FOR THIS TENANT SPACE ACCORDING TO FMC
 403.3.1.1 AND TABLE 403.3.1.1. THE TABLE 403.3.1.1
 SHOULD BE USE FOR THE OCCUPANT COUNT FOR EACH SPACE AND
 NOT THE ARCHITECTURAL OCCUPANCY COUNTS.
  
 PROVIDE THE MECHANICAL EQUIPMENT SIZING CALCULATIONS
 FOR THIS TENANT SPACE. FEC C403.2.1
  