Plan Review Notes For Permit 22051173 |
Permit Number |
22051173 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2022-06-10 16:42:48 | PROVIDE A COMPLETE OUTDOOR AIR CALCULATION FOR EACH USE | | OF SPACE FOR THIS TENANT SPACE ACCORDING TO FMC | | 403.3.1.1 AND TABLE 403.3.1.1. THE TABLE 403.3.1.1 | | SHOULD BE USE FOR THE OCCUPANT COUNT FOR EACH SPACE AND | | NOT THE ARCHITECTURAL OCCUPANCY COUNTS. | | | | PROVIDE THE MECHANICAL EQUIPMENT SIZING CALCULATIONS | | FOR THIS TENANT SPACE. FEC C403.2.1 | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | |
|