Plan Review Notes
Plan Review Notes For Permit 22051144
Permit Number 22051144
Review Stop P
Sequence Number 1
Notes
Date Text
2022-06-01 11:43:011ST REVIEW FBC-2020 RES. PLUMBING
 PERMIT- 22051144
 6/1/2022
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET 3: PLEASE PROVIDE THE PUMP CURVE ON THE SHEET
 MARKED UP TO SHOW THE TDH AND FLOW RATE OF THE SYSTEM-
 SECS. 4.4.9, 4.4.9.1 ANSI/APSP/ICC-7 & R4501.7.2 &
 R4501.7.3 FBC RES.
  
 2) ENERGY COMPLIANCE: REFER TO SEC. R403.10 FBC EC AND
 PROVIDE DETAILS OR NOTES VERIFYING INSTALLATIONS OF-
 A) A READILY ACCESSIBLE ON-OFF SWITCH FOR THE HEAT
 PUMP.
 B) TIME SWITCHES OR OTHER CONTROL METHODS TO
 AUTOMATICALLY TURN OFF OF THE HEAT PUMP AND POOL PUMP.
 C) POOL COVER.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  