Notes |
Date |
Text |
2022-06-21 10:11:34 | FIRE COMMENTS: | | | | 1.GENERAL NOTES SECTION ON THE PLAN NOTE #6 STATES | | ?SMOKE DETECTORS EXISTING IN ALL BEDROOMS ARE | | INTERCONNECTED.? THE PLAN INDICATES THE LOFT AREA IS | | FOR STORAGE. PROVIDE CLEAR INDICATION OF THE USE OF THE | | SPACE AND IF IT WILL INCLUDE SLEEPING AREAS. PROVIDE | | DETAILS ON ANY EXISTING FIRE ALARM DEVICES AND/OR | | SYSTEMS IN PLACE. | | | | 2.CLARIFY IF THE BUILDING IS EQUIPPED OR NOT, WITH A | | FIRE SPRINKLER SYSTEM. | | | | 3.IF STORAGE OCCUPANCY, DECLARE IF IT IS LOW, ORDINARY | | OR HIGH HAZARD CONTENTS. | | | | 4.PROVIDE A CLEAR TRAVEL DISTANCE FROM THE MOST REMOTE | | LOCATION TO REACH THE EXIT. | | | | 5.PROVIDE TYPE OF DOOR HARDWARE TO BE INSTALLED | | INCLUDING LOCK TYPES. | | | | NFPA 101, CHAPTER 42 | | | | C. WALKER | | | | (561) 804-4762 | | | | [email protected] | | |
|