Plan Review Notes For Permit 22051074 |
Permit Number |
22051074 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2022-05-26 13:12:30 | FIRE COMMENTS: | | THE PLAN INDICATES THE EXISTING DOOR THAT OPENS INTO | | THE KITCHEN WILL HAVE A WALL ERECTED. THIS WALL IS IN A | | CORRIDOR AND IS REQUIRED TO HAVE A FIRE RESISTANCE | | RATING. THERE IS NO DETAIL PROVIDED ON HOW THIS WILL BE | | ACHIEVED. IF THE DOOR IS TO REMAIN, AND A WALL ERECTED | | ONLY ON THE INSIDE OF THE RESIDENTIAL UNIT, PROVIDE | | DETAILS ON HOW THE DOOR WILL BE SECURED AND SIGNAGE ON | | THE EXTERIOR INDICATING THAT THE DOOR IS NOT TO BE USED | | FOR ENTRY. | | PROVIDE SUPPORTING DOCUMENTATION ON PROPOSED NEW CARPET | | TO BE INSTALLED TO COMPLY WITH NFPA 101, 10.2.7 | | | | C. WALKER | | | | 561-804-4762 | | | | [email protected] | | |
|