Date |
Text |
2022-07-07 16:13:26 | 1ST REVIEW FBC-2020 PLUMBING |
| PERMIT- 22051043 |
| 7/7/2022 |
| |
| CODES IN EFFECT: |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| 2020 |
| FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEET 1: UNDER PLUMBING NOTES PLEASE LIST THE |
| APPLICABLE CODES FOR THE PROJECT- SEC. 107.2.1 WPB. |
| |
| 2) SHEETS 1 & 2: FAIR HOUSING ACT COMPLIANCE. THE |
| CONDOMINIUMS AT 101 N. CLEMATIS- THE LOFT WERE DESIGNED |
| AND CONSTRUCTED IN ACCORDANCE WITH THE FAIR HOUSING ACT |
| DESIGN GUIDELINES, THEREFORE THE PROPOSED ALTERATIONS |
| SHALL ALSO BE IN COMPLIANCE WITH THE GUIDELINES. THE |
| FAIR HOUSING ACCESSIBILITY GUIDELINES ARE INCLUDED IN |
| THE FLORIDA ACCESSIBILITY CODE- 2020 7TH EDITION AND |
| THE FAIR HOUSING DESIGN ACT MANUAL. PLEASE INCLUDE THE |
| FAIR HOUSING COMPLIANCE INFORMATION IN THE APPLICABLE |
| CODE LIST. REFER TO PAGE 7-8 OF THE MANUAL FOR |
| COMPLIANCES APPLICABLE TO THE LOFT UNITS. |
| |
| 3) SHEET 2: REFER TO PAGES 7.34- 7.38 FHDA MANUAL |
| INDICATE ON THE PLANS WHICH OF THE TWO BATHROOM TYPES |
| IS THE BASIS OF DESIGN- SPECIFICATION TYPE A OR B ON |
| THE PLANS. IT APPEARS THAT THE MAIN BATHROOM IS BEING |
| DESIGNED AS A TYPE B WHICH WILL PROVIDE A HIGHER LEVEL |
| OF ACCESSIBILITY. PLEASE PROVIDE AN ENLARGED FLOOR PLAN |
| DRAWING OF THE BATHROOM WITH THE FHDA DETAILS: |
| PAGES 7.40-7.46 WATER CLOSET CLEAR FLOOR SPACE DIAGRAM |
| AND DIMENSIONS. |
| PAGES 7.47- 7.52: LAVATORY AND VANITY CLEAR FLOOR SPACE |
| DIAGRAM AND DIMENSIONS. |
| PAGES 7.56- 7.59: SHOWER CLEAR FLOOR SPACE DIAGRAM AND |
| DIMENSIONS AND CONTROL LOCATIONS INCLUDING SHOWER |
| DIMENSIONS. |
| PAGE 7.37: A 30X48-INCH CLEAR FLOOR DIAGRAM OUTSIDE THE |
| SWING OF THE DOOR. |
| PAGE 3.5: A 32-INCH CLEAR DOOR OPENING. |
| PAGE 4.3: ACCESSIBLE ROUTE TO THE BATHROOM. |
| |
| 4) SHEET 2: PROVIDE FHDA COMPLIANCE DETAILS FOR THE |
| POWDER ROOM: |
| PAGE 3.5: A 32-INCH CLEAR DOOR OPENING. |
| PAGE 4.3: ACCESSIBLE ROUTE TO THE ROOM. |
| |
| 5) SHEET 2: REFER TO FHDA MANUAL PAGES 7.1- 7.6 AND |
| SHOW THE CLEAR FLOOR SPACES FOR SINKS AND APPLIANCES. |
| |
| 6) SHEET 2: REFER TO FDHA MANUAL PAGES 6.12- 6.13 AND |
| PROVIDE SHOWER GRAB BAR REINFORCEMENT DETAILS. |
| |
| PLEASE NOTE: AS AN ALTERNATIVE TO MEETING THE |
| GUIDELINES FOR THE PROPOSED ALTERATIONS TO UNITS 411, |
| 412, AND 413, THE OWNER AND DESIGNER OF RECORD MAY |
| PROVIDE A SIGNED AND NOTARIZED AFFIDAVIT WHICH WOULD |
| INDICATE ACKNOWLEDGEMENT THAT THE PROPOSED DESIGN DOES |
| NOT MEET THE REQUIREMENTS OF THE FAIR HOUSING |
| ACCESSIBILITY GUIDELINES, BUT WILL ALSO REQUIRE THE |
| OWNER TO AGREE TO REVERT THE UNIT BACK TO COMPLIANCE AT |
| TIME OF SALE IF REQUESTED BY THE BUYER. IF THIS OPTION |
| IS CHOSEN, PLEASE SEND AN EMAIL TO [email protected] AND I |
| WILL SEND A COPY OF THE FAIR HOUSING AFFIDAVIT. |
| |
| 7) SHEET 2: PROVIDE AN EQUIPMENT SCHEDULE FOR THE NEW |
| TANKLESS WATER- SEC. 502.1 FBC P. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |