Plan Review Notes For Permit 22051041
Permit Number 22051041
Review Stop P
Sequence Number 2
Notes
Date Text
2022-07-11 09:22:322ND PLUMBING REVIEW
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2017 WPB AMENDS 107.3.5.1.3 - PLEASE PROVIDE A
 PLUMBING PAGE WITH THE SANITARY RISERS FOR THE NEW
 CONNECTIONS.
  
 2, 2017 WPB AMENDS 107.2.1 - PLEASE PROVIDE THE
 EXISTING AND PROPOSED FLOOR PLANS FOR CLARITY OF WORK
 TO BE DONE.
  
 3. 2020 FPC 901.2.1 - SEVERAL FIXTURES SHOWN ON THE
 RISER DIAGRAM A CURRENTLY CONNECTED TO THE WASTE
 SANITARY STACK WITHOUT A VENT BETWEEN THE FIXTURE TRAP
 AND THE CONNECTION TO THE STACK. PLEASE PROVIDE A CODE
 COMPLIANT RISER DIAGRAM THAT IS PROPERLY VENTED
 ACCORDING TO CHAPTER 9 OF THE FLORIDA PLUMBING CODE.
  
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  