2022-07-15 13:54:00 | |
| SHOW HOW THE RETURN AIR WILL WILL TRAVEL FROM THE ROOMS |
| WITH THE DOORS BACK TO THE AHU. |
| |
| FMC 601.6 BALANCED RETURN AIR. RESTRICTED RETURN AIR |
| OCCURS IN |
| BUILDINGS WHEN RETURNS ARE LOCATED IN CENTRAL ZONES AND |
| CLOSED |
| INTERIOR DOORS IMPEDE AIR FLOW TO THE RETURN GRILL OR |
| WHEN CEILING |
| SPACES ARE USED AS RETURN PLENUMS AND FIRE WALLS |
| RESTRICT |
| AIR MOVEMENT FROM ONE PORTION OF THE RETURN PLENUM TO |
| ANOTHER. PROVISIONS SHALL BE MADE IN BOTH RESIDENTIAL |
| AND |
| COMMERCIAL BUILDINGS TO AVOID UNBALANCED AIR FLOWS AND |
| PRESSURE |
| DIFFERENTIALS CAUSED BY RESTRICTED RETURN AIR. PRESSURE |
| DIFFERENTIALS |
| ACROSS CLOSED DOORS WHERE RETURNS ARE CENTRALLY |
| LOCATED SHALL BE LIMITED TO 0.01-INCH WC (2.5 PASCALS) |
| OR LESS. |
| PRESSURE DIFFERENTIALS ACROSS FIRE WALLS IN CEILING |
| SPACE PLENUMS |
| SHALL BE LIMITED TO 0.01-INCH WC (2.5 PASCALS) BY |
| PROVIDING |
| AIR DUCT PATHWAYS OR AIR TRANSFER PATHWAYS FROM THE |
| HIGH PRESSURE ZONE TO THE LOW ZONE. |
| EXCEPTIONS: |
| 1. TRANSFER DUCTS MAY ACHIEVE THIS BY INCREASING THE |
| RETURN TRANSFER 11/2 TIMES THE CROSS SECTIONAL AREA |
| (SQUARE INCHES) OF THE SUPPLY DUCT ENTERING THE ROOM OR |
| SPACE IT IS SERVING AND THE DOOR HAVING AT LEAST AN |
| UNRESTRICTED |
| 1-INCH UNDERCUT TO ACHIEVE PROPER RETURN AIR |
| BALANCE. |
| 2. TRANSFER GRILLES SHALL USE 50 SQUARE INCHES (OF |
| GRILLE |
| AREA) TO 100 CFM (OF SUPPLY AIR) FOR SIZING |
| THROUGH-THEWALL |
| TRANSFER GRILLES AND USING AN UNRESTRICTED 1-INCH |
| UNDERCUTTING OF DOORS TO ACHIEVE PROPER RETURN AIR |
| BALANCE. |
| 3. HABITABLE ROOMS ONLY SHALL BE REQUIRED TO MEET THESE |
| REQUIREMENTS FOR PROPER BALANCED RETURN AIR EXCLUDING |
| BATHROOMS, CLOSETS, STORAGE ROOMS AND LAUNDRY ROOMS, |
| EXCEPT THAT ALL SUPPLY AIR INTO THE MASTER SUITE SHALL |
| BE |
| INCLUDED. |
| |