Plan Review Notes
Plan Review Notes For Permit 22051029
Permit Number 22051029
Review Stop B
Sequence Number 2
Notes
Date Text
2022-07-19 10:11:23WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 22051029
 ADD: 2427 PRESIDENTIAL WAY # 304
 CONT: AVANTE CONSTRUCTION & RENOVATION
 TEL: 561-756-6200
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUES. JULY 19TH/2022
 ACTION: DENIED
  
 1-2) COMPLIED
  
 3) 2ND REQUEST. PLEASE NOTE, THE RESPONSE AND SHEET A-1
 STATE LAMINATED/ ENGINEERED WOOD FLOORING AND PROFLEX
 90 UNDERLAYMENT. THE CITY OF W. P. B. IS IN RECEIPT OF
 PROFLEX SUPER SIM 90 FOR TILE AND OR MARBLE ONLY NOT
 LAMINATED/ ENGINEERED WOOD FLOORING.
 PROFLEX DOES HAVE TESTING REPORTS FOR PROFLEX LV-200
 FOR LAMINATED FLOORS. REPORTS HAVE BEEN FORWARDED IN A
 RETURN E-MAIL TO YOUR OFFICE.
 1ST ROUND OF COMMENTS. THE FLOOR PLAN NOR ANY OF THE
 OTHER PLANS INDICATE THE TYPE OF FLOOR FINISH AND TYPE
 OF UNDERLAYMENT. FLOOR INSULATION/ UNDERLAYMENT (FBC-B
 2020) FOR TILE, STONE, MARBLE, VINYL (LYT/ LYP),
 LAMINATE FLOORING AND WOOD FLOORING ALL NEED TO HAVE
 HAD THE SOUND UNDERLAYMENT TESTED FLOOR ASSEMBLIES TO
 THE FOLLOWING STANDARDS AND MEET THE QUALIFICATIONS
 LISTED UNDER EACH OF THE STANDARDS FOR A 6 INCH
 CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING:
 PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR
 TYPE II BUILDINGS SHOWING COMPLIANCE WITH:
  
 3A) FBC-B 2020 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492.
  
 3B) FBC-B 2020 1207.2 AIR-BORNE SOUND. WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E
 90.
  
 3C1) FLAME SPREAD- FBC-B 2020 603.1. EXCEPTION 2. (TILE
 & MARBLE) INSULATION INSTALLED BETWEEN A FINISHED FLOOR
 AND SOLID DECKING WITHOUT INTERVENING AIRSPACE SHALL BE
 ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN
 200.
  
 3C2) FBC-B 804.4.4.1 SOFT FLOOR FINISHES (LVT/ LPT OR
 LAMINATED OR ENGINEERED WOOD FLOORING) WITHIN TENANT
 SPACE. INTERIOR FLOOR COVERING MATERIALS SHALL COMPLY
 WITH THE REQUIREMENTS OF THE COC FF-1 ?PILL TEST? (CPSC
 16 CFR PART 1630) OR WITH ASTM D2859.
  
 4) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  