2022-07-19 10:11:23 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| SERVICES/ BUILDING DIVISION |
| 2020 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 22051029 |
| ADD: 2427 PRESIDENTIAL WAY # 304 |
| CONT: AVANTE CONSTRUCTION & RENOVATION |
| TEL: 561-756-6200 |
| E-MAIL: [email protected] |
| |
| 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| 2ND REVIEW |
| DATE: TUES. JULY 19TH/2022 |
| ACTION: DENIED |
| |
| 1-2) COMPLIED |
| |
| 3) 2ND REQUEST. PLEASE NOTE, THE RESPONSE AND SHEET A-1 |
| STATE LAMINATED/ ENGINEERED WOOD FLOORING AND PROFLEX |
| 90 UNDERLAYMENT. THE CITY OF W. P. B. IS IN RECEIPT OF |
| PROFLEX SUPER SIM 90 FOR TILE AND OR MARBLE ONLY NOT |
| LAMINATED/ ENGINEERED WOOD FLOORING. |
| PROFLEX DOES HAVE TESTING REPORTS FOR PROFLEX LV-200 |
| FOR LAMINATED FLOORS. REPORTS HAVE BEEN FORWARDED IN A |
| RETURN E-MAIL TO YOUR OFFICE. |
| 1ST ROUND OF COMMENTS. THE FLOOR PLAN NOR ANY OF THE |
| OTHER PLANS INDICATE THE TYPE OF FLOOR FINISH AND TYPE |
| OF UNDERLAYMENT. FLOOR INSULATION/ UNDERLAYMENT (FBC-B |
| 2020) FOR TILE, STONE, MARBLE, VINYL (LYT/ LYP), |
| LAMINATE FLOORING AND WOOD FLOORING ALL NEED TO HAVE |
| HAD THE SOUND UNDERLAYMENT TESTED FLOOR ASSEMBLIES TO |
| THE FOLLOWING STANDARDS AND MEET THE QUALIFICATIONS |
| LISTED UNDER EACH OF THE STANDARDS FOR A 6 INCH |
| CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING: |
| PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR |
| TYPE II BUILDINGS SHOWING COMPLIANCE WITH: |
| |
| 3A) FBC-B 2020 1207.3 STRUCTURE-BORNE SOUND. |
| FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492. |
| |
| 3B) FBC-B 2020 1207.2 AIR-BORNE SOUND. WALLS, |
| PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING |
| DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR |
| AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E |
| 90. |
| |
| 3C1) FLAME SPREAD- FBC-B 2020 603.1. EXCEPTION 2. (TILE |
| & MARBLE) INSULATION INSTALLED BETWEEN A FINISHED FLOOR |
| AND SOLID DECKING WITHOUT INTERVENING AIRSPACE SHALL BE |
| ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN |
| 200. |
| |
| 3C2) FBC-B 804.4.4.1 SOFT FLOOR FINISHES (LVT/ LPT OR |
| LAMINATED OR ENGINEERED WOOD FLOORING) WITHIN TENANT |
| SPACE. INTERIOR FLOOR COVERING MATERIALS SHALL COMPLY |
| WITH THE REQUIREMENTS OF THE COC FF-1 ?PILL TEST? (CPSC |
| 16 CFR PART 1630) OR WITH ASTM D2859. |
| |
| 4) A TRANSMITTAL LETTER / NARRATIVE LISTING THE |
| ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| THE REVISION MADE, IDENTIFYING THE SHEET OR |
| SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| ANTICIPATED COOPERATION. |
| |
| PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| REVIEW CYCLE. |
| |
| |
| MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM |
| PART-TIME/ SEMI-RETIRED. |
| |
| IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET |
| BACK INTO THE OFFICE CALL |
| (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL. |
| THANK YOU. |
| |
| JAMES A. WITMER BN, PX, SFP, CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES |
| DEPARTMENT |
| 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| TEL: 561-805-6717 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |