Plan Review Notes For Permit 22051029 |
Permit Number |
22051029 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2022-05-31 10:51:02 | FIRE COMMENTS: | | SMOKE ALARM LOCATIONS ARE NOT INDICATED ON THE PLAN | | SUBMITTAL. NFPA 101, 30.3.4.6.1 | | THE TYPE OF FINISHED FLOORING IS NOT INDICATED ON THE | | PLAN SUBMITTAL. NFPA 101, 10.2.7 | | ANY AND ALL WORK ON THE LIFE SAFETY SYSTEMS (FIRE | | ALARM/FIRE SPRINKLERS) SHALL BE PERFORMED UNDER | | SEPARATE PERMITS AND SHOP DRAWINGS BY PROPERLY LICENSED | | CONTRACTORS. | | THE LIFE SAFETY SYSTEMS (FIRE ALARM/FIRE SPRINKLERS) | | SHALL REMAIN ACTIVE DURING ALL PHASES OF DEMOLITION AND | | CONSTRUCTION. ANY IMPAIRMENTS TO ANY LIFE SAFETY SYSTEM | | LASTING MORE THAN 4 CONTINUOUS HOURS IN DURATION WILL | | REQUIRE THE IMPLEMENTATION OF FIRE WATCH. | | C. WALKER | | 561-804-4762 | | [email protected] | | |
|