2022-07-06 11:15:20 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| SERVICES/ BUILDING DIVISION |
| 2020 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 22051029 |
| ADD: 2427 PRESIDENTIAL WAY # 304 |
| CONT: AVANTE CONSTRUCTION & RENOVATION |
| TEL: 561-756-6200 |
| E-MAIL: [email protected] |
| |
| 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: WED. JULY 06TH/2022 |
| ACTION: DENIED |
| |
| 1) SHEET A-1 PROPOSED FLOOR PLAN: |
| 1A) THE OCCUPANCY IS DECLARED AS R, R1, R2 OR R3? |
| PLEASE REVIEW THE 2020 FBC-BUILDING CODE RESIDENTIAL |
| GROUP R SECTION 310. |
| |
| 1B) THE CONSTRUCTION TYPE IS LISTED AS TYPE III. PLEASE |
| REVIEW 2020 FBC-BUILDING CODE TABLE 504.4. PLEASE NOTE |
| THIS IS A 24-STORY BUILDING, IN THE 2020 FBC-B TABLE |
| 504.4 FOR A R2 OCCUPANCY THE BUILDING TYPE WOULD BE |
| I-A, PLEASE UPDATE THE PLANS. |
| |
| 1C) DOOR & WINDOW NOTES. WINDOWS, DOORS & FRENCH GLASS |
| DOOR INSTALLATION SHALL BE IN ACCORDANCE WITH |
| MANUFACTURES SPECIFICATION SET FORTH IN THE APPROVED |
| PRODUCT CONTROL APPROVAL. PLEASE NOTE THIS REVIEW CYCLE |
| NO PRODUCT APPROVALS WERE SUBMITTED. |
| |
| COMPONENTS & CLADDING. PLEASE SUBMIT THE COMPONENTS AND |
| CLADDING PRODUCT APPROVALS. 2020 FBC-B 1609.1.2 |
| PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS & |
| CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, |
| ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/ |
| 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| (31)(A) EXTERIOR DOORS, MULLIONS & ROOF HATCHES. |
| (B) WINDOWS & MULLIONS |
| (C) PANEL WALLS: STOREFRONTS |
| |
| 1D) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS |
| WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE |
| 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING (SHOP |
| DRAWING STAMP OF APPROVAL) BY THE DESIGNER OF RECORD |
| PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP DRAWINGS ETC. |
| |
| |
| 1E) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY IN THE |
| PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF |
| RECORD AND BEFORE SUBMISSION TO THE BUILDING |
| DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE |
| IDENTIFY THE OPENING WIDTH & HEIGHT, SILL HEIGTH, TYPE |
| OF GLAZING, MULLION SIZE, LENGTH IF UNREINFORCED OR |
| REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND |
| ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2020 FBC-B |
| 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE |
| INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER?S |
| INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE |
| PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED |
| BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS. |
| |
| |
| 1F) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF |
| THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE |
| PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE |
| TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO |
| THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. |
| DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR |
| APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED |
| DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST |
| THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS |
| FOR REVIEW BY THE BUILDING OFFICIAL. |
| |
| DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| OFFICIAL. |
| |
| 2) NONE OF THE PLANS PROVIDE WIND DESIGN CRITERIA. 2020 |
| FBC-B 1603.1.4 WIND DESIGN CRITERIA. |
| THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL |
| BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE |
| DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE |
| STRUCTURE: |
| |
| 2.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST), |
| MILES PER HOUR AND NOMINAL DESIGN WIND SPEED, VASD, AS |
| DETERMINED IN ACCORDANCE WITH SECTION 1609.3.1. |
| |
| 2.2. RISK CATEGORY. |
| |
| 2.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE |
| THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2. |
| HEIGHT AND EXPOSURE. ASCE 7-16 TABLE 30.3.1. NOTE 24 |
| FLOOR BUILDING, NEGATIVE PRESSURES TAKEN FROM ROOF |
| LEVEL. |
| |
| 2.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT. |
| |
| 2.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR |
| COMPONENTS AND CLADDING MATERIALS SPECIFICALLY DESIGNED |
| BY THE REGISTERED DESIGN PROFESSIONAL RESPONSIBLE FOR |
| THE DESIGN OF THE STRUCTURE, PSF. |
| |
| 2.6. TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT & |
| EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE |
| BUILDING. ASCE 7-10 TABLE 30.3.1. 1609.3.1 WIND SPEED |
| CONVERSION VULT TO VASD. |
| |
| 2.7) 2020 FBC-B 1709.5.1 HABITAT SPACES, WATER |
| INTRUSION. EXTERIOR DOORS AND WINDOWS. EXCEPTION # 2. |
| SILL LIMITING FACTOR. |
| |
| 3) THE FLOOR PLAN NOR ANY OF THE OTHER PLANS INDICATE |
| THE TYPE OF FLOOR FINISH AND TYPE OF UNDERLAYMENT. |
| FLOOR INSULATION/ UNDERLAYMENT (FBC-B 2020) FOR TILE, |
| STONE, MARBLE, VINYL (LYT/ LYP), LAMINATE FLOORING AND |
| WOOD FLOORING ALL NEED TO HAVE HAD THE SOUND |
| UNDERLAYMENT TESTED FLOOR ASSEMBLIES TO THE FOLLOWING |
| STANDARDS AND MEET THE QUALIFICATIONS LISTED UNDER EACH |
| OF THE STANDARDS FOR A 6 INCH CONCRETE FLOOR ASSEMBLY/ |
| NO DROPPED CEILING: |
| PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR |
| TYPE II BUILDINGS SHOWING COMPLIANCE WITH: |
| |
| 3A) FBC-B 2020 1207.3 STRUCTURE-BORNE SOUND. |
| FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492. |
| |
| 3B) FBC-B 2020 1207.2 AIR-BORNE SOUND. WALLS, |
| PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING |
| DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR |
| AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E |
| 90. |
| |
| 3C1) FLAME SPREAD- FBC-B 2020 603.1. EXCEPTION 2. (TILE |
| & MARBLE) INSULATION INSTALLED BETWEEN A FINISHED FLOOR |
| AND SOLID DECKING WITHOUT INTERVENING AIRSPACE SHALL BE |
| ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN |
| 200. |
| |
| 3C2) FBC-B 804.4.4.1 SOFT FLOOR FINISHES (LVT/ LPT OR |
| LAMINATED OR ENGINEERED WOOD FLOORING) WITHIN TENANT |
| SPACE. INTERIOR FLOOR COVERING MATERIALS SHALL COMPLY |
| WITH THE REQUIREMENTS OF THE COC FF-1 ?PILL TEST? (CPSC |
| 16 CFR PART 1630) OR WITH ASTM D2859. |
| |
| 4) A TRANSMITTAL LETTER / NARRATIVE LISTING THE |
| ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| THE REVISION MADE, IDENTIFYING THE SHEET OR |
| SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| ANTICIPATED COOPERATION. |
| |
| PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| REVIEW CYCLE. |
| |
| |
| MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM |
| PART-TIME/ SEMI-RETIRED. |
| |
| IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET |
| BACK INTO THE OFFICE CALL |
| (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL. |
| THANK YOU. |
| |