Plan Review Notes
Plan Review Notes For Permit 22051015
Permit Number 22051015
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2022-07-19 12:04:28THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE APPEAARS TO BE 2 DICONNECT BOXES, HOWEVER,
 THEY ARE CENTRALLY LOCATED AND COULD BE INACCESSIBLE IN
 AN EMERGENCY EVENT.
  
 11.12 PHOTOVOLTAIC SYSTEMS.
  
 11.12.1 PHOTOVOLTAIC SYSTEMS SHALL BE IN ACCORDANCE
 WITH SEC TION 11.12 AND NFPA 70
  
 11.12.2.1* MARKING. PHOTOVOLTAIC SYSTEMS SHALL BE
 PERMANENTLY MARKED AS SPECIFIED IN THIS SUBSECTION
  
 11.12.2.1.1 RAPID SHUTDOWN MARKING. BUILDINGS WITH A PV
 SYSTEM SHALL BE PROVIDED WITH PERMANAENT LABLES AS
 DESCRIBED IN 11.12.2.1.1.1 THROUGH 11.12.2.1.1.7.
  
 PLEASE REVIEW AND RELOCATE A SINGLE(1) DISCONNECT FOR
 THE ENTIRE ROOF AT/NEAR THE EXIT FROM THE ROOF
 STAIRWELL.
  
  
  
 2) THERE ARE INDICATIONS OF 2 FDC'S ALONG THE 4' FIRE
 PATH, HOWEVER, THE REQUIRMENT OF THE CODE STATES 4'
 CLEAR AROUND THE STANDPIPE.
  
 11.12.2.2.3.2 PATHWAYS. PATHWAYS SHALL BE ESTABLISHED
 AS FOLLOWS:
 (1) PATHWAYS SHALL BE OVER AREAS CAPABLE OF SUPPORTING
 THE LIVE
 LOAD OF FIRE FIGHTERS ACCESSING THE ROOF.
 (2) CENTERLINE AXIS PATHWAYS SHALL BE PROVIDED IN BOTH
 AXES OF
 THE ROOF.
 (3) CENTERLINE AXIS PATHWAYS SHALL RUN WHERE THE ROOF
 STRUC TURE IS CAPABLE OF SUPPORTING THE LIVE LOAD OF
 FIRE FIGHTERS
 ACCESSING THE ROOF.
 (4) PATHWAYS SHALL BE IN A STRAIGHT LINE NOT LESS THAN
 4 FT
 (1219 MM) CLEAR TO SKYLIGHTS, VENTILATION HATCHES, AND
 ROOF STANDPIPES.
 (5) PATHWAYS SHALL PROVIDE NOT LESS THAN 4 FT (1219 MM)
 CLEAR
 AROUND ROOF ACCESS HATCHES WITH AT LEAST ONE NOT LESS
 THAN
 4 FT (1219 MM) CLEAR PATHWAY TO THE PARAPET OR ROOF
 EDGE
  
 PLEASE REVIEW AND AND PROVIDE A 4' RADUIS AT EACH FDC.
  
  
  
 3) THERE ARE INDICATIONS OF PATHWAYS AROUND THE ROOF
 LINE AND OTHER AREAS, HOWEVER, IT IS NOT CLEAR THE
 DIMENSION OF ALL AREAS.
  
 11.12.2.2.3.1 ACCESS. A MINIMUM 4 FT (1219 MM) WIDE
 CLEAR
 PERIMETER SHALL BE PROVIDED AROUND THE EDGES OF THE
 ROOF FOR
 BUILDINGS WITH A LENGTH OR WIDTH OF 250 FT (76.2 M) OR
 LESS ALONG
 EITHER AXIS. A MINIMUM 6 FT (1829 MM) WIDE CLEAR
 PERIMETER
 SHALL BE PROVIDED AROUND THE EDGES OF THE ROOF FOR
 BUILDINGS
 HAVING LENGTH OR WIDTH GREATER THAN 250 FT (76.2 M)
 ALONG
 EITHER AXIS
  
 PLEASE REVIEW AND CORRECT/PROVIDE DETAIALED DIMENSIONS.
  
 4) THERE ARE INDICATIONS OF ELECTRICAL CONDUIT/CABLING
 THROUGHOUT THE ROOF/PANEL STRUCTURES, HOWEVER, THERE
 ARE NO CLEAR INDICATIONS OF THE LOCATION/ROUTING OF THE
 ELECTIRCAL SYSTEM COMPONENTS.
  
 11.12.2.1.3* CONDUIT, RACEWAY, ENCLOSURE, CABLE
 ASSEMBLY,
 AND JUNCTION BOX MARKINGS. MARKING SHALL BE REQUIRED ON
 ALL
 INTERIOR AND EXTERIOR DC CONDUITS, RACEWAYS,
 ENCLOSURES, CABLE
 ASSEMBLIES, AND JUNCTION BOXES.
 (1) EXPOSED RACEWAYS...
 (2) COVERSOR ENCLOSURES OF PULL/JUNCTION BOXS
 (3) CONDUIT BODIES IN WHICH ANY OF THE AVAILABLE
 CONDUIT OPENINGS ARE UNUSED.
  
 11.12.2.1.3.1 MARKING LOCATIONS. MARKING SHALL BE
 PLACED ON.....
 ALL DC CONDUITS, RACEWAYS, ENCLOSURES, AND CABLE
 ASSEMBLIES EVERY 10 FT (3048 MM), AT TURNS, AND ABOVE
 AND BELOW PENETRA TIONS. MARKING SHALL BE PLACED ON ALL
 DC COMBINER AND JUNC TION BOXES.
  
 PLEASE REVIEW AND PROVIDE.
  
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  