Notes |
Date |
Text |
2022-07-18 13:28:44 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | | | 1. FBC B 1015.6, IT APPEARS THAT THE EQUIPMENT IS | | PROPOSED LESS THAN 10' FROM THE ROOF EDGE. REVISE PLAN | | TO SHOW COMPLIANCE WITH THE REQUIREMENT FOR GUARDS. | | | | 2. S001, THE WIND DESIGN CRITERIA IS NOT CLEAR. IT | | APPEARS TO STATE THAT THE BUILDING IS EXPOSURE D, | | 170MPH, THE PV IS C, 180MPH. CLARIFY, APPEARS THIS | | LOCATION IS EXPOSURE D. | | | | 3. S001, CODE TABLE, REVISE TO STATE THE GOVERNING | | CODE(S) PER FS553. IBC IS NOT A GOVERNING CODE, THE | | RESIDENTIAL CODE IS NOT APPLICABLE FOR THIS PROJECT AS | | THIS IS NOT CONSIDERED A ONE OR TWO FAMILY DWELLING. |
|