Plan Review Notes
Plan Review Notes For Permit 22051006
Permit Number 22051006
Review Stop E
Sequence Number 5
Notes
Date Text
2023-05-26 12:56:04ELECTRIC REVIEW FAILED
  
 1) THERE IS MORE THAN ONE INTERCONNECTION RISER DIAGRAM
 IN THE SUBMITTAL, ONE OF WHICH WAS FAILED PREVIOUSLY,
 ACCORDING TO RECORDS ON FILE, THE NEW DIAGRAM DOES NOT
 EXIST AT THIS LOCATION.
 IT APPEARS THAT GUESSING IS NOT A PROPER STRATEGY FOR
 DRAWING ELECTRICAL RISER DIAGRAMS. IT WOULD BE
 SUGGESTED THAT A QUALIFIED PERSON BE SENT TO SURVEY THE
 ACTUAL ELECTRIC CONFIGURATION IN PLACE, AND SUBMIT A
 CODE COMPLIANT PV SYSTEM INTERCONNECTION DRAWING NEC
 215.5.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  