Plan Review Notes
Plan Review Notes For Permit 22051006
Permit Number 22051006
Review Stop E
Sequence Number 2
Notes
Date Text
2022-09-14 13:42:10ELECTRIC REVIEW FAILED
 1) PLANS STILL LACK CLARITY ON RISER DIAGRAM, CONDUIT
 RUNS FROM ELECTRIC ROOM TO ROOF(PROVIDE DETAILS ON THE
 MECHANICAL CHASE). ALSO PROVIDE CLEARANCE DETAILS FOR
 NEW EQIPMENT IN ELECTRIC ROOM. FBC 107.2 NEC 215.5 AND
 NEC 110.26
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  