2022-07-19 12:12:22 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| 1) THERE APPEAARS TO BE 1 DICONNECT BOX, HOWEVER, IT IS |
| LOCATED AT A DISTANCE FROM THE STAIRWELL AND COULD BE |
| INACCESSIBLE IN AN EMERGENCY EVENT. |
| |
| THERE IS NO DISCONNECT LOCATED AT THE OTHER STAIRWELL |
| ACCESS. |
| |
| 11.12 PHOTOVOLTAIC SYSTEMS. |
| |
| 11.12.1 PHOTOVOLTAIC SYSTEMS SHALL BE IN ACCORDANCE |
| WITH SEC TION 11.12 AND NFPA 70 |
| |
| 11.12.2.1* MARKING. PHOTOVOLTAIC SYSTEMS SHALL BE |
| PERMANENTLY MARKED AS SPECIFIED IN THIS SUBSECTION |
| |
| 11.12.2.1.1 RAPID SHUTDOWN MARKING. BUILDINGS WITH A PV |
| SYSTEM SHALL BE PROVIDED WITH PERMANAENT LABLES AS |
| DESCRIBED IN 11.12.2.1.1.1 THROUGH 11.12.2.1.1.7. |
| |
| PLEASE REVIEW AND RELOCATE THAT DISCONNECT CLOSER TO |
| THE STAIRWELL AND PROVICE A 2ND DICONNECT AT THE OTHER |
| STAIRWELL, |
| |
| |
| |
| 2) THERE ARE INDICATIONS OF PATHWAYS AROUND THE ROOF |
| LINE AND OTHER AREAS, HOWEVER, IT IS NOT CLEAR THE |
| DIMENSION OF ALL AREAS. |
| |
| 11.12.2.2.3.1 ACCESS. A MINIMUM 4 FT (1219 MM) WIDE |
| CLEAR |
| PERIMETER SHALL BE PROVIDED AROUND THE EDGES OF THE |
| ROOF FOR |
| BUILDINGS WITH A LENGTH OR WIDTH OF 250 FT (76.2 M) OR |
| LESS ALONG |
| EITHER AXIS. A MINIMUM 6 FT (1829 MM) WIDE CLEAR |
| PERIMETER |
| SHALL BE PROVIDED AROUND THE EDGES OF THE ROOF FOR |
| BUILDINGS |
| HAVING LENGTH OR WIDTH GREATER THAN 250 FT (76.2 M) |
| ALONG |
| EITHER AXIS |
| |
| |
| PLEASE REVIEW AND CORRECT/PROVIDE DETAIALED DIMENSIONS. |
| |
| |
| |
| 3) THERE ARE INDICATIONS OF ELECTRICAL CONDUIT/CABLING |
| THROUGHOUT THE ROOF/PANEL STRUCTURES, HOWEVER, THERE |
| ARE NO CLEAR INDICATIONS OF THE LOCATION/ROUTING OF THE |
| ELECTIRCAL SYSTEM COMPONENTS. |
| |
| 11.12.2.1.3* CONDUIT, RACEWAY, ENCLOSURE, CABLE |
| ASSEMBLY, |
| AND JUNCTION BOX MARKINGS. MARKING SHALL BE REQUIRED ON |
| ALL |
| INTERIOR AND EXTERIOR DC CONDUITS, RACEWAYS, |
| ENCLOSURES, CABLE |
| ASSEMBLIES, AND JUNCTION BOXES. |
| (1) EXPOSED RACEWAYS... |
| (2) COVERSOR ENCLOSURES OF PULL/JUNCTION BOXS |
| (3) CONDUIT BODIES IN WHICH ANY OF THE AVAILABLE |
| CONDUIT OPENINGS ARE UNUSED. |
| |
| 11.12.2.1.3.1 MARKING LOCATIONS. MARKING SHALL BE |
| PLACED ON..... |
| ALL DC CONDUITS, RACEWAYS, ENCLOSURES, AND CABLE |
| ASSEMBLIES EVERY 10 FT (3048 MM), AT TURNS, AND ABOVE |
| AND BELOW PENETRA TIONS. MARKING SHALL BE PLACED ON ALL |
| DC COMBINER AND JUNC TION BOXES. |
| |
| PLEASE REVIEW AND PROVIDE. |
| |
| |
| |
| 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| ABOVE. |
| |
| |
| 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| |
| PETER LEDUC |
| FIRE MARSHAL |