Plan Review Notes
Plan Review Notes For Permit 22051006
Permit Number 22051006
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2022-07-19 12:12:22THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE APPEAARS TO BE 1 DICONNECT BOX, HOWEVER, IT IS
 LOCATED AT A DISTANCE FROM THE STAIRWELL AND COULD BE
 INACCESSIBLE IN AN EMERGENCY EVENT.
  
 THERE IS NO DISCONNECT LOCATED AT THE OTHER STAIRWELL
 ACCESS.
  
 11.12 PHOTOVOLTAIC SYSTEMS.
  
 11.12.1 PHOTOVOLTAIC SYSTEMS SHALL BE IN ACCORDANCE
 WITH SEC TION 11.12 AND NFPA 70
  
 11.12.2.1* MARKING. PHOTOVOLTAIC SYSTEMS SHALL BE
 PERMANENTLY MARKED AS SPECIFIED IN THIS SUBSECTION
  
 11.12.2.1.1 RAPID SHUTDOWN MARKING. BUILDINGS WITH A PV
 SYSTEM SHALL BE PROVIDED WITH PERMANAENT LABLES AS
 DESCRIBED IN 11.12.2.1.1.1 THROUGH 11.12.2.1.1.7.
  
 PLEASE REVIEW AND RELOCATE THAT DISCONNECT CLOSER TO
 THE STAIRWELL AND PROVICE A 2ND DICONNECT AT THE OTHER
 STAIRWELL,
  
  
  
 2) THERE ARE INDICATIONS OF PATHWAYS AROUND THE ROOF
 LINE AND OTHER AREAS, HOWEVER, IT IS NOT CLEAR THE
 DIMENSION OF ALL AREAS.
  
 11.12.2.2.3.1 ACCESS. A MINIMUM 4 FT (1219 MM) WIDE
 CLEAR
 PERIMETER SHALL BE PROVIDED AROUND THE EDGES OF THE
 ROOF FOR
 BUILDINGS WITH A LENGTH OR WIDTH OF 250 FT (76.2 M) OR
 LESS ALONG
 EITHER AXIS. A MINIMUM 6 FT (1829 MM) WIDE CLEAR
 PERIMETER
 SHALL BE PROVIDED AROUND THE EDGES OF THE ROOF FOR
 BUILDINGS
 HAVING LENGTH OR WIDTH GREATER THAN 250 FT (76.2 M)
 ALONG
 EITHER AXIS
  
  
 PLEASE REVIEW AND CORRECT/PROVIDE DETAIALED DIMENSIONS.
  
  
  
 3) THERE ARE INDICATIONS OF ELECTRICAL CONDUIT/CABLING
 THROUGHOUT THE ROOF/PANEL STRUCTURES, HOWEVER, THERE
 ARE NO CLEAR INDICATIONS OF THE LOCATION/ROUTING OF THE
 ELECTIRCAL SYSTEM COMPONENTS.
  
 11.12.2.1.3* CONDUIT, RACEWAY, ENCLOSURE, CABLE
 ASSEMBLY,
 AND JUNCTION BOX MARKINGS. MARKING SHALL BE REQUIRED ON
 ALL
 INTERIOR AND EXTERIOR DC CONDUITS, RACEWAYS,
 ENCLOSURES, CABLE
 ASSEMBLIES, AND JUNCTION BOXES.
 (1) EXPOSED RACEWAYS...
 (2) COVERSOR ENCLOSURES OF PULL/JUNCTION BOXS
 (3) CONDUIT BODIES IN WHICH ANY OF THE AVAILABLE
 CONDUIT OPENINGS ARE UNUSED.
  
 11.12.2.1.3.1 MARKING LOCATIONS. MARKING SHALL BE
 PLACED ON.....
 ALL DC CONDUITS, RACEWAYS, ENCLOSURES, AND CABLE
 ASSEMBLIES EVERY 10 FT (3048 MM), AT TURNS, AND ABOVE
 AND BELOW PENETRA TIONS. MARKING SHALL BE PLACED ON ALL
 DC COMBINER AND JUNC TION BOXES.
  
 PLEASE REVIEW AND PROVIDE.
  
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  