2022-06-15 14:28:27ELECTRIC REVIEW
 1) PLEASE PROVIDE CLARITY ON RISER WIRING DIAGRAM
 TRANSFORMER, MAIN PANEL BOARD (ASSUME THIS IS HOUSE
 PANEL, PLEASE USE MATCHING NOMENCLATURES) VOLTAGES FOR
 ALL EQIPMENT. NEC 215.5
 2 )PLEASE PROVIDE A FLOOR PLAN SHOWING LOCATION OF
 ELECTRIC ROOM AND RELEVANT ELECTRIC EQUIPMENT. FBC
 107.2
 3) PLEASE PROVIDE DETAILS FOR CONDUIT RUNS FROM ROOF TO
 ELECTRIC EQUIPMENT.FBC 107.2
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  